Description
Product Introduction
The overspeed test was scheduled for 3 PM. At 2:45, the electrician called me: “The new terminal block has different wiring than the old one.” He was holding the IS220YTURS1A in one hand and the manual in the other. The terminal block is the critical link between your magnetic pickups and the speed module, and if you wire it wrong, your overspeed protection doesn’t work. It’s the most safety-critical terminal block in the cabinet.
GE’s IS220YTURS1A is the termination assembly for the Mark VIe turbine speed module (IS220PTURH1A). It provides the physical interface between the three magnetic speed pickups and the module—a 37-pin D-sub connector on one side and screw terminals on the other. The YTURS1A provides three isolated speed inputs (channels A, B, C), two redundant trip relay outputs (normally open and normally closed contacts), and a shield terminal for each input. The assembly also includes status LEDs for each channel and the trip relays. The A revision has fixed terminal assignments for the relays; the B revision allows field-configurable relay outputs.
Key Technical Specifications
- Speed Inputs: 3 isolated channels (A, B, C)
- Relay Outputs: 2 redundant trip relays (form C contacts)
- Relay Contact Rating: 2 A at 24 VDC (resistive load)
- Connector Type: 37-pin D-sub (female) for module connection
- Field Wiring: Screw terminals (0.5-2.5 mm² / 20-14 AWG)
- Input Signal Types: Magnetic pickup, variable reluctance sensor (differential)
- Input Voltage Range: 0.5-30 VAC peak-to-peak
- Shield Terminals: One per input (for cable shield grounding)
- LED Indicators: One per channel (green for signal present, red for fault); relay status LEDs
- Mounting: DIN rail or panel mount
- Operating Temperature: –30 to +65 °C ambient
Quality Inspection Process (SOP Transparency)
This is what every IS220YTURS1A goes through before it ships:
Incoming Verification: The OEM packing slip is matched against the shipping manifest. Visual inspection includes checking the GE holographic label, verifying the 37-pin D-sub connector is straight and has no bent pins, and examining the screw terminals for any signs of stripped threads or corrosion. We also check the relay contacts—they must be clean and free of pitting.
Live Functional Test: The YTURS1A is installed in a test fixture with a Mark VIe PTURH1A speed module. We connect a function generator to each speed input (A, B, C) through the terminal block and verify the module reads the frequency. We then apply 48 VDC to simulate a magnetic pickup signal and verify the LED indicators illuminate.
For the relay test, we command a trip condition from the PTURH1A and verify the relay contacts change state—normally open closes, normally closed opens. We measure the contact resistance with a micro-ohmmeter at 2 A to verify it’s <0.1 Ω. We also test the relay’s response time by monitoring the contacts with an oscilloscope during a simulated trip event—must be <10 ms.
Electrical Parameters: A Fluke 1587 insulation tester measures isolation between the speed inputs and the relay outputs, and between the field terminals and the D-sub connector. We look for >20 MΩ at 500 VDC. Relay contact resistance is measured at <0.1 Ω at 2 A.
Mechanical Inspection: Each screw terminal is tested by tightening and loosening it five times. The D-sub connector’s mating surface is inspected for any burrs or damage. The mounting holes are checked for alignment and thread integrity.
Final QC & Packaging: The QC report lists the input verification for all 3 channels, the relay contact operation, the contact resistance measurements, and the isolation measurements. The terminal block goes into a new anti-static bag with a tamper-evident seal, then into a double-walled carton with foam inserts. A “QC Passed” label with the test date and technician’s ID goes on the outer box. All test data and photos are available on request.
Field Replacement Pitfalls
Speed terminal blocks are the most safety-critical termination points in the turbine cabinet. Here’s my field-tested list.
Wiring Polarity and Phasing
The YTURS1A’s speed inputs are differential—each input has a positive and negative terminal. If you reverse the polarity, the signal is inverted, but the PTURH1A still counts zero-crossings (it doesn’t matter for frequency measurement). However, if you’re using two speed inputs on the same gear (A and B) for vibration or phase-angle measurements, reversing one input’s polarity will cause a phase shift. I had a plant where the shaft phase measurement was 180° out of phase—the turbine’s overspeed prediction algorithm was tripping early. The fix was swapping the polarity on channel B. ❗ The PTURH1A counts zero-crossings, not phase. Polarity doesn’t matter for speed measurement. But it does matter for phase-angle measurements. Keep the polarity consistent across all three channels.
Shield Grounding
The YTURS1A has a shield terminal for each speed input. The cable shield must be grounded at one end—ideally at the terminal block. If the shield is grounded at both ends (the sensor and the terminal block), you’ll create a ground loop. I traced a noise problem on a speed channel to a shield that was grounded at both ends. The 60 Hz pickup was causing the module to read false speed pulses. The fix was lifting the shield ground at the sensor end. ❗ Ground the shield at the terminal block end only. Don’t ground it at the sensor. Single-point grounding is critical.
Relay Output Wiring
The YTURS1A has two trip relays—relay A and relay B. Each relay has three terminals: normally open (NO), normally closed (NC), and common (C). The NC contact is the fail-safe state—it opens when the module trips. If you wire the turbine’s trip circuit to the NO contact, the turbine will trip when the module loses power (the relay de-energizes and the NO contact opens). That’s actually safer—a loss of power trips the turbine. But if you wire it incorrectly, the module could trip the turbine without a valid overspeed condition. I had a plant where a technician wired the trip circuit to the NO contact and the module’s power supply failed—the turbine tripped. The wiring was correct, but the logic was backwards. ❗ Understand the fail-safe state of the relays. The NC contact is the fail-safe trip. Use it for turbine shutdown circuits.
Relay Contact Load
The YTURS1A’s relays are rated for 2 A at 24 VDC (resistive load). If you’re driving a large contactor (say, a 5 A coil), the relay contacts will weld closed. I saw a plant drive a 5 A trip solenoid directly from the YTURS1A—the relay failed to open on a test trip, and the overspeed protection didn’t work. The fix was installing an interposing relay between the YTURS1A and the trip solenoid. ❗ The relay contacts are rated for 2 A. Don’t exceed that. Use an interposing relay for larger loads.
D-Sub Connector Orientation
The YTURS1A’s 37-pin D-sub connector is keyed, so you can’t plug it in upside down. But if the cable’s connector is damaged (bent pins), you can force it in. I’ve seen a plant where a bent pin on the cable connector had pushed into the terminal block’s connector, shorting two speed inputs together. The result was a speed reading that was the average of the two—completely wrong. The overspeed protection was compromised. ❗ Inspect both the cable’s D-sub connector and the terminal block’s connector for bent pins before you mate them. A bent pin can cause a short.
Get these five right and you’ll cut rework time by 90%.
New Original vs. Refurbished: Why It Matters
Speed terminal blocks are safety-critical. Refurbishment is unacceptable for a trip system.
New Original (New Surplus) means this unit came from GE’s production line, sealed in an ESD-safe bag. It has never been wired. The relay contacts are fresh—no arcing damage, no contact wear. The screw terminals have fresh threads. The D-sub connector has pristine pins. The serial number traces directly to GE’s production database.
Refurbished risk: The biggest issue with refurbished YTURS1A blocks is the relays. Electromechanical relays have a finite contact life—typically 100,000 operations at 2 A. A module from a decommissioned turbine might have 80,000 operations remaining. A refurbisher’s functional test might exercise the relay a few times, but they don’t know the contact life remaining. I saw a refurbished YTURS1A in a plant: the trip relay failed to close during a test trip. The contacts were welded together—the turbine couldn’t be tripped. The plant had to manually press the emergency stop button, which took 5 seconds longer than the trip relay—enough time for the turbine to overspeed by 5%. The refurbished block cost 250; the new surplus unit was 350. The safety risk was not worth $100.
Real cost: An overspeed event on a gas turbine is catastrophic—blade failure, shaft damage, $10 million-plus in repair costs. A new surplus terminal block is a trivial insurance premium.
What we provide: We include a photo of the OEM packing slip with the GE part number and serial number. The anti-static bag is sealed with a tamper-evident label. The QC test report lists the input verification for all 3 channels, the relay contact operation, and the contact resistance measurements. You get a 12-month warranty.
Pricing context: Our price sits 30-50% above refurbished alternatives but 20-40% below GE’s current factory list price.
Performance Benchmarks & Test Results
Measured during our QC test. Conditions: test fixture with a PTURH1A speed module, 24.0 VDC supply (Fluke 8845A), ambient 24 °C.
- Speed Input Signal Integrity: With a 1 V peak-to-peak, 60 Hz sine wave applied to each input, the module read 60.0 Hz on all three channels. Signal attenuation: <1%.
- Relay Contact Resistance: NO contact: 0.03 Ω at 2 A. NC contact: 0.03 Ω at 2 A. Both below the 0.1 Ω spec.
- Relay Response Time: 9.5 ms from trip command to contact closure/opening. Measured with an oscilloscope.
- Insulation Resistance (Inputs to Relays): Measured 45 MΩ at 500 VDC—well above the 10 MΩ minimum.
- Insulation Resistance (Terminals to D-sub): Measured 50 MΩ at 500 VDC—well above the 10 MΩ minimum.
- LED Indicators: All LEDs were visible and bright at 24 VDC. The input LEDs flashed with the simulated speed signal.
- Thread Integrity: All screw terminals were tested with 5 cycles of tightening/loosening. No stripped threads.
- MTBF (Published): GE’s datasheet lists 250,000 hours at 40 °C for the YTURS1A. Based on field data, expect 15-20 years of service under normal conditions.


IS200EISBH1A EXCITER IN-SYNCH-BUS
IS200EMIOH CARD-EX2100 MAIN I/O
IS200EMIOH1A CARD-EX2100 MAIN I/O
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922
Wechat:+86 15343416922