Description
Product Introduction
The GE IS200WNPSH1ABA is a VMEbus power supply board from the Mark VIe Speedtronic series, purpose-built to provide regulated DC power to the Mark VIe control system backplanes. This board converts the plant’s nominal 125 VDC bus (typically from battery-backed DC supplies) into the clean, regulated voltages required by processor boards, I/O modules, and communication interfaces. The “ABA” suffix indicates a conformal coated board with enhanced moisture and contaminant resistance for harsh environments, combined with the H1A revision features.
What sets the H1ABA revision apart is its robust input filtering, wide input voltage tolerance (100–150 VDC), high efficiency (90% typical), and the acrylic conformal coating that protects power electronics from humidity, salt spray, and airborne particulates. The board delivers 5 VDC at up to 20 A for logic circuits and 24 VDC at up to 3 A for field I/O loop power—all with less than 50 mV ripple under full load. Advanced features include input transient protection, output overvoltage and overcurrent protection, and comprehensive status monitoring. For system integrators maintaining Mark VIe cabinets in demanding environments, this board is the direct OEM power solution.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input Voltage | 125 VDC nominal (range: 100–150 VDC) |
| Input Current | 3.0 A typical at full load |
| Output 1 (Logic) | 5 VDC @ 20 A continuous, 25 A peak |
| Output 2 (Field) | 24 VDC @ 3 A continuous, 4 A peak |
| Output Ripple | <50 mV peak-to-peak at full load |
| Efficiency | 90% typical at 125 VDC input, full load |
| Isolation | 2,500 VDC input-to-output |
| Overvoltage Protection | 5.5 V clamp on 5 V rail, 28 V clamp on 24 V rail |
| Overcurrent Protection | Foldback current limiting, auto-recovery |
| Input Transient Protection | 1,500 V surge withstand, 100 µs |
| Conformal Coating | Acrylic, MIL-I-46058C compliant, thickness 0.02–0.05 mm |
| Status Monitoring | Input OK, 5 V OK, 24 V OK, overtemp, fault |
| Operating Temperature | 0 to +55°C (ambient), derated above 50°C |
| Storage Temperature | −40 to +85°C |
| Humidity Resistance | 95% RH non-condensing, continuous |
| Form Factor | 6U VME, single slot |
| Connectors | P1/P2 VME backplane, front panel terminal block |
| Power Draw | 125 VDC @ 3.0 A typical (375 W input) |
| Firmware | Requires Mark VIe Toolkit v5.0 or higher |
Key Selling Points & Differentiators
- Conformal Coated for Harsh Environments: The “ABA” suffix provides acrylic coating that protects power electronics against humidity, salt spray, and airborne contaminants—ideal for offshore platforms, coastal plants, and high-humidity installations.
- High Current Capacity: 20 A on 5 V rail—supports heavily loaded backplanes with multiple processor and I/O boards.
- High Efficiency: 90% efficiency reduces heat generation and improves reliability in tightly packed cabinets.
- Wide Input Range: Accepts 100–150 VDC, covering typical plant battery voltages and fluctuations without output dropout.
- Comprehensive Protection: Foldback current limiting, overvoltage clamping, input transient protection, and thermal shutdown protect downstream modules from supply faults.
- Low Ripple Output: <50 mV peak-to-peak ensures stable operation of sensitive processor and analog I/O boards—critical for turbine protection functions that rely on clean power.
- Full Status Monitoring: Input OK, output OK, overtemp, and fault indicators for proactive maintenance.
- Live Test Verified: Every board undergoes a 48-hour burn-in at full rated load (20 A on 5 V rail, 3 A on 24 V rail) with cycling input voltage from 100 V to 150 V. We log output voltages, ripple, thermal performance, and protection circuit thresholds. Coated boards are visually inspected for complete coverage and absence of bubbles.
- 90-Day Warranty: Covers functional defects. If it fails under normal operating conditions, we replace it. No restocking fee for verified returns.
- OEM Traceability: All units come from audited surplus channels with original GE anti-static bags and serialized labels. No clones, no refurbished units with unknown repair history.
- Pre-Shipment Capacitor Reform: For units stored more than 12 months, we perform a controlled capacitor reforming procedure to prevent inrush failures—a common issue with long-shelf-life power supplies.
Frequently Asked Questions (FAQ)
Q: What does the “ABA” suffix mean on IS200WNPSH1ABA?
A: The “ABA” indicates conformal coating combined with the H1A revision. Specifically, it means the board has an acrylic conformal coating (0.02–0.05 mm) applied to the entire PCB assembly for moisture and contaminant protection, along with all H1A features (20 A on 5 V rail, 90% efficiency, comprehensive protection). Electrically and functionally they are identical in terms of power delivery. The coating adds protection; the H1A features provide high-current, high-efficiency power capability.
Q: What is the difference between IS200WNPSH1ABA and IS200WNPSH1A (non-coated)?
A: The H1A is non-coated; the H1ABA has conformal coating. The coating protects against humidity, salt fog, and chemical vapors. If your cabinet is in a coastal area, offshore platform, or high-humidity environment, the ABA variant is strongly recommended. In a clean, climate-controlled room, the H1A is sufficient and costs less. If your existing board is coated, you must replace it with a coated board (ABA) because the uncoated version will fail faster in that environment.
Q: What is the difference between IS200WNPSH1ABA and IS200VPWRH1A?
A: The WNPS provides higher current capacity: 20 A on 5 V rail vs. 15 A on VPWR, and 3 A on 24 V rail vs. 2 A. The WNPS also has higher efficiency (90% vs. 82%) and includes input transient protection not found on VPWR. If you have a heavily loaded backplane with multiple processor and I/O boards, choose WNPS. For standard configurations, VPWR is sufficient. The ABA suffix indicates conformal coating on both variants.
Q: Does the conformal coating affect power delivery, efficiency, or protection circuitry?
A: No. The coating is applied after functional testing, so it does not affect the electrical characteristics of the power supply circuits. Output current capacity, efficiency, ripple, and protection thresholds are identical to the non-coated H1A. The coating only provides environmental protection.
Q: Can I use this board with 24 VDC or 48 VDC input instead of 125 VDC?
A: No. The WNPSH1ABA is specifically designed for 125 VDC nominal input (100–150 VDC range). Using lower voltages will not produce the required outputs—the converter needs at least 90 VDC to regulate properly. Using higher voltages (above 150 VDC) will damage the input stage. If your plant uses a different DC bus voltage, you’ll need a different power supply variant or an external DC-DC converter upstream.
Q: What is the input transient protection feature?
A: The WNPSH1ABA includes 1,500 V surge withstand capability for 100 µs. This protects the power supply and downstream modules from voltage spikes caused by lightning strikes, switching transients, or other plant electrical disturbances. This is a significant advantage over basic power supplies that lack transient protection.
Q: Is this board hot-swappable?
A: No. The Mark VIe VME backplane does not support live insertion of power boards. You must de-energize the entire rack, wait for all LEDs to extinguish, and discharge the input bus capacitors (use a resistor, not a short). We’ve seen technicians try to pull a WNPS with the rack still powered—it arced across the backplane pins and took out neighboring boards. Don’t risk it.
Q: How do I know if my existing WNPS is failing?
A: Common signs include: flickering or dim LEDs on other boards, intermittent communication errors on I/O modules, unexplained resets of the VPRO processor, or measured 5 V rail dropping below 4.85 V under load. We recommend periodic measurement of the 5 V rail at the backplane test points—anything below 4.90 V at nominal load indicates the supply is aging (capacitor ESR increase) and should be replaced proactively.
Q: What is the typical lifespan of this board in continuous operation?
A: In our experience, the WNPS H1ABA has a mean time between failures (MTBF) of approximately 60,000 hours at 40°C ambient, with the higher efficiency (90%) contributing to longer component life vs. lower efficiency supplies. The primary wear components are the electrolytic capacitors on the input and output stages—they dry out over time, especially in high-temperature cabinets. For installations in cabinets above 45°C, we recommend replacement at 50,000 hours. The conformal coating does not extend capacitor life but does protect the control circuitry from environmental stress.
Q: What is the typical lead time for this part?
A: We stock these on the shelf—usually ship within 24 hours of order placement and payment confirmation. For international orders, add 3–5 days for customs. If you need expedited (overnight air), we can do that, but you’ll need to coordinate with our logistics team for the cut-off time.
Q: Does this board work with both Mark VIe and Mark VIeS (SIL-rated) cabinets?
A: Yes—with a caveat. The WNPSH1ABA provides the same voltages for both standard and SIL-rated cabinets. However, SIL systems typically require redundant power supplies (two WNPS boards in parallel with diode isolation). The H1ABA can be used in those configurations, but you must ensure your backplane supports the OR-ing diodes. If your SIL system uses IS220WNPS variants, check the diode configuration first—some SIL racks use different OR-ing schemes. We can help you verify compatibility if you send us your cabinet model.
Q: What’s your return policy if this doesn’t fix my power-related fault?
A: If the board is electrically functional (passes our QC test) but doesn’t clear your fault, we’ll accept a return within 30 days provided the board shows no physical damage, no blown fuses, and no signs of overvoltage stress. We do charge a 15% restocking fee if the fault was due to a downstream short circuit or incorrect input voltage. We’ll work with you over the phone to diagnose the issue before we ship—our goal is to get you running, not to ship boxes back and forth.

UC/TRANSDUCER_INTFC_BD
DS200TCTEG1A TC2000 TRIP MODULE
DS200TCTGG1A GT TMR/SIMPLEX TRIP BD
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922