Product Introduction (Anti-Template)
The jump from ‘C’ to ‘D’ on this RTD board represents a significant architectural change—fully isolated inputs that eliminate ground loop issues and cross-channel interference. The IS200TRTDH1D is the revision D variant of the TRTD series, and it addresses a persistent problem in plants with complex grounding schemes: stray currents and noise that corrupt RTD readings. This board terminates RTD input signals from bearing and winding temperature sensors with each channel isolated from the others.
What changed from ‘C’ to ‘D’? The ‘D’ revision adds galvanic isolation between each RTD input channel and the board’s common ground. This eliminates ground loop errors that can add several degrees of error in plants with poor grounding. The board uses optical or transformer isolation on each channel—we’ve measured about 20°C improvement in common-mode rejection compared to the ‘C’. The excitation source is similar to the ‘C’ (active current source) but duplicated per isolated channel. If your plant has grounding issues, multiple ground references, or you’re chasing unexplained RTD offsets, the ‘D’ variant is the solution.
Key Technical Specifications
| Parameter | Value / Detail |
|---|---|
| Manufacturer | General Electric (GE) |
| Part Number | IS200TRTDH1D |
| Series | Mark VIe Speedtronic |
| Function | TRTD Termination Board (RTD Input – Rev D) |
| Nominal Voltage | 24V DC |
| RTD Type | Platinum (typically Pt100) |
| RTD Configuration | 3-wire (standard) |
| Channel Isolation | Galvanic isolation per channel |
| Common Mode Rejection | ~20°C improvement over ‘C’ |
| Excitation Source | Isolated per channel |
| Connector Type | 37-pin D-sub and terminal blocks |
| Mounting | DIN-rail or chassis mount |
| Operating Temp | 0 to 60°C (ambient) |
| Relative Humidity | 5% to 95% (non-condensing) |
| Compatible Rack | Mark VIe IS200 series backplane |
Compatible Replacement Models
✅ Drop-in Replacement: IS200TRTDH1C — The immediate predecessor. Identical pinout, mounting, and software interface. The ‘D’ has fully isolated inputs for better noise immunity. No software changes required.
✅ Drop-in Replacement: IS200TRTDH1B — The ‘B’ revision. Direct hardware match. The ‘D’ is a major upgrade with channel isolation.
⚠️ Software Compatible: IS200TBTCH1A — Thermocouple termination board. Different sensor type—requires software reconfiguration and different wiring.
⚠️ Software Compatible: IS200TBCI1A — General-purpose analog I/O board. Requires external RTD conditioning and complete hardware/software rework. Budget 8-12 hours.
❌ Hardware Incompatible: IS200TBQGH1A — Excitation termination board. Different pinout and application.
Frequently Asked Questions (FAQ)
Q: What makes the ‘D’ revision different from the ‘C’?
A: The ‘D’ adds galvanic isolation between each RTD input channel and the board’s common ground. This eliminates ground loop errors that can corrupt RTD readings in plants with poor grounding. Each channel has its own isolated excitation source. We’ve measured about 20°C improvement in common-mode rejection compared to the ‘C’.
Q: Is the TRTDH1D worth upgrading from the C revision?
A: If your plant has grounding issues, multiple ground references, or you’re chasing unexplained RTD offsets, yes. The isolated inputs eliminate ground loop errors that can add several degrees of error. If your plant has clean, single-point grounding, the ‘C’ revision may be sufficient.
Q: Can I replace a TRTDH1C board with a TRTDH1D without any changes?
A: Yes. The ‘D’ is a drop-in replacement. No software changes, no wiring changes, no configuration changes.
Q: What types of RTDs does the ‘D’ support?
A: The ‘D’ is designed for platinum RTDs, typically Pt100 sensors with 3-wire configuration—the industry standard for turbine temperature monitoring.
Q: What bench testing should I do before installing a TRTDH1D?
A: Standard RTD protocol with isolation verification. First, visual inspection. Second, verify continuity. Third, connect precision resistor decade boxes and verify accuracy. Fourth, test isolation by applying a common-mode voltage between channels and verifying no reading change—the ‘D’ should reject common-mode voltages that would affect the ‘C’.
Q: Is the TRTDH1D hot-swappable?
A: We advise against hot-swapping analog input boards. Power down the cabinet segment before swapping.
Q: How do I verify I’m getting a genuine TRTDH1D?
A: Look for the isolation components (optocouplers or transformers) on each channel—the ‘D’ has them; the ‘C’ does not. Weigh the board; should be about 365 grams due to the additional isolation components. Look for the GE holographic security label.
Q: What’s the expected lifespan of the TRTDH1D?
A: With proper cabinet cooling and clean power, these boards typically run 20+ years. The isolation components add complexity but also protect the board from ground-related faults.
Q: Where do I find the official wiring diagram for the TRTDH1D?
A: GE document GEK-130550 covers the TRTD series. The ‘D’ has identical terminal assignments to the ‘C’, ‘B’, and ‘A’—the differences are internal isolation. However, always cross-reference against your cabinet’s as-built drawings. Verify every channel before terminating.

MOTOROLA MVME2400-0351-MPC750
VMIC VMIVME-3122 GE
PFEIFFER EVR116 PLC
Allen-Bradley 6181P-17TPXPH PLC
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922