Description
Product Introduction (Anti-Template)
When your control logic needs to switch something that isn’t a solenoid or actuator—think annunciators, indicator lights, or interposing relays—this is the board you reach for. The IS200TREGH1A is the TREGH (Terminal Board Relay Output – General Purpose) variant for the Mark VIe system, designed to terminate general-purpose relay output signals for turbine control and protection applications. This board handles the interface between the Mark VIe controller and relay-driven field devices.
The ‘H1A’ designation indicates a specific variant of the TREGH series, with the ‘H1’ likely referring to a particular channel configuration. The ‘A’ revision represents minor refinements—improved relay contact ratings and updated component selection. Compared to the base IS200TREGH1, the ‘A’ adds better contact material on the relays for longer life in cycling applications. This board is a drop-in replacement for the IS200TREGH1, with no software changes required. It complements the TPRO series—use TPRO for triac outputs (solenoids, actuators) and TREGH for general-purpose relay outputs.
Key Technical Specifications
| Parameter | Value / Detail |
|---|---|
| Manufacturer | General Electric (GE) |
| Part Number | IS200TREGH1A |
| Series | Mark VIe Speedtronic |
| Function | TREGH Termination Board (Relay Output – General Purpose) |
| Nominal Voltage | 24V DC |
| Output Type | Relay (general-purpose) |
| Channel Count | Dependent on H1 configuration |
| Relay Contact Material | Improved in ‘A’ revision |
| Connector Type | 37-pin D-sub and terminal blocks |
| Mounting | DIN-rail or chassis mount |
| Operating Temp | 0 to 60°C (ambient) |
| Relative Humidity | 5% to 95% (non-condensing) |
| Compatible Rack | Mark VIe IS200 series backplane |
Compatible Replacement Models
✅ Drop-in Replacement: IS200TREGH1 — The base revision without the ‘A’ suffix. Identical pinout, mounting, and software interface. The ‘A’ revision has improved relay contact material and minor component updates. No software changes required.
⚠️ Software Compatible: IS200TPROH1A — Triac output board. Similar functionality but uses triacs instead of mechanical relays. Different switching characteristics—triacs handle AC loads, relays handle both AC and DC. Requires software reconfiguration if replacing.
⚠️ Software Compatible: IS200TBCI1A — General-purpose analog I/O termination board. Can be used with external interposing relays, but requires complete hardware and software rework. Budget 6-8 hours plus validation.
❌ Hardware Incompatible: IS200TBQGH1A — Excitation termination board. Different pinout and application. Not applicable.
Frequently Asked Questions (FAQ)
Q: What types of loads can the TREGH board switch?
A: The TREGH board is designed for general-purpose relay outputs, typically used for switching annunciators, indicator lights, interposing relays, and other low-to-moderate power loads. The relay contacts are rated for both AC and DC loads.
Q: How does the TREGH differ from the TPRO board?
A: The TREGH uses mechanical relays for general-purpose switching. The TPRO uses triacs for power switching (solenoids, actuators). TREGH is for applications where you need dry contacts (isolated switching). TPRO is for directly driving power loads.
Q: What improvements does the ‘A’ revision have over the base TREGH1?
A: The ‘A’ revision uses improved contact material on the relays—better resistance to arcing and longer life in cycling applications. The contact ratings are slightly higher as well.
Q: Can I replace a TREGH1 board with a TREGH1A without any changes?
A: Yes. The ‘A’ is a drop-in replacement. No software changes, no wiring changes, no configuration changes.
Q: Is the TREGH board hot-swappable?
A: We advise against hot-swapping relay boards. Mechanical relays can arc if switched under load while being removed. Power down the cabinet segment before swapping.
Q: What bench testing should I do before installing a TREGH board?
A: Standard relay output protocol. First, visual inspection. Second, verify continuity between each terminal block and its corresponding D-sub pin. Third, measure coil resistance and contact resistance. Fourth, apply power and verify each relay actuates correctly. Fifth, run a 24-hour cycle test at 50°C ambient to verify relay contact stability.
Q: What happens if a relay contact welds or fails?
A: The output may stay energized or fail to energize. The Mark VIe system may detect the failure through feedback monitoring. Replace the board. The improved contact material on the ‘A’ revision reduces the risk of welding.
Q: How do I verify I’m getting a genuine TREGH board?
A: Check the relay markings against GE documentation. Weigh the board; it should be about 365 grams due to the relays. Look for the GE holographic security label.
Q: Where do I find the official wiring diagram for the TREGH1A?
A: GE document GEK-130543 covers the TREGH series. The H1 variant is detailed in the section specific to that configuration. Pay special attention to contact ratings—AC vs DC loads have different de-rating requirements. Always cross-reference against your cabinet’s as-built drawings.

DDK NFT-201RM1-S PC
GE IC754VSF12CTD
GE 369-HI-R-M-0-0-0-E
ICS TRIPLEX(ROCKWELL) T8451
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922