IS200TPROH1B | 24V Power Triac Termination H1B

  • Model: IS200TPROH1B
  • Brand: General Electric (GE)
  • Series: Mark VIe Speedtronic
  • Core Function: TPRO (Terminal Board Power Relay Output) revision B termination board with improved triac driver protection for power switching applications.
  • Product Type: Termination / I/O Board
  • Key Specs: 24V DC, triac/relay outputs, 37-pin D-sub connectors, enhanced snubber protection
  • Condition: New Surplus. Factory-sealed anti-static bag.
Manufacturer:

Our extensive catalogue, including , is available now for dispatch to the worldwide.
  • Email: jiedong@sxrszdh.com
  • Phone / Wechat:+86 15340683922

Description

 

Product Introduction (Anti-Template)

That ‘B’ suffix on the end of this model number is your first clue that GE addressed something specific with this board—in this case, it’s the protection circuitry on the output drivers. The IS200TPROH1B is the revision B variant of the TPRO series, and it represents a meaningful upgrade to the power switching termination board for Mark VIe systems. This board handles triac or relay outputs for solenoids, actuators, and contactors, but with better protection against the kind of electrical abuse that kills output boards in the field.

What changed from the ‘A’ to the ‘B’? GE added enhanced snubber circuitry on each output channel—RC networks designed to suppress voltage spikes when switching inductive loads. The result is about 30% better protection against back-EMF from solenoids and valves. The board also uses upgraded triac packages with higher surge current ratings. Compared to the TPROH1A, the ‘B’ reduces the risk of output failure when you’re driving heavy inductive loads. If you’ve had triac failures on your existing boards, the ‘B’ variant is a direct upgrade path.

 

Key Technical Specifications

Parameter Value / Detail
Manufacturer General Electric (GE)
Part Number IS200TPROH1B
Series Mark VIe Speedtronic
Function TPRO Termination Board (Power Relay Output – Rev B)
Nominal Voltage 24V DC
Output Type Triac or relay (configuration-dependent)
Channel Count Dependent on H1 configuration
Snubber Protection Enhanced RC networks per channel
Triac Surge Rating Improved over ‘A’ revision
Connector Type 37-pin D-sub and terminal blocks
Mounting DIN-rail or chassis mount
Operating Temp 0 to 60°C (ambient)
Relative Humidity 5% to 95% (non-condensing)
Compatible Rack Mark VIe IS200 series backplane

 

Compatible Replacement Models

✅ Drop-in Replacement: IS200TPROH1A — The immediate predecessor. Identical pinout, mounting, and software interface. The ‘B’ has enhanced snubber protection and upgraded triacs. No software changes required. If you’re driving inductive loads, the ‘B’ is the better choice.

✅ Drop-in Replacement: IS200TPROH1 — The base revision. Direct hardware match but lacks the enhanced protection and upgraded components. Works, but the ‘B’ offers better reliability.

⚠️ Software Compatible: IS200TPR0H2B — A different TPRO variant with a ‘0’ in the model. Check pinout compatibility—some variants are drop-in, others require verification. Consult GE documentation before substituting.

⚠️ Software Compatible: IS200TBCI1A — General-purpose analog I/O termination board. Can be used with external interposing relays, but requires a complete hardware and software rework. Budget 6-8 hours plus validation.

❌ Hardware Incompatible: IS200TBQGH1A — Excitation termination board. Different pinout and application. Not applicable.

 

Frequently Asked Questions (FAQ)

Q: What makes the ‘B’ revision different from the ‘A’?

A: Two major improvements. First, GE added enhanced snubber circuitry (RC networks) on each output channel to suppress voltage spikes from inductive loads. We’ve measured about 30% better spike suppression on the ‘B’ compared to the ‘A’. Second, the triac packages were upgraded to higher surge current ratings, reducing the risk of failure during transient conditions.

Q: Is the TPROH1B worth upgrading from the A revision?

A: If you’re switching inductive loads—solenoids, valves, contactors—the answer is yes. The enhanced snubber protection directly addresses the failure mode that kills output boards in those applications. If you’re switching purely resistive loads, the A revision is likely fine.

Q: Can I replace a TPROH1A board with a TPROH1B without any changes?

A: Yes. The ‘B’ is a drop-in replacement. No software changes, no wiring changes, no configuration changes. The board functions identically from the system’s perspective.

Q: What types of loads can the TPROH1B switch?

A: The TPROH1B is designed for triac or relay outputs, typically used for switching solenoids, contactors, actuators, and other power devices. The enhanced snubber protection makes it particularly suitable for inductive loads.

Q: What bench testing should I do before installing a TPROH1B?

A: Standard power switching protocol with snubber verification. First, visual inspection—look for the additional snubber components (RC networks) on the output paths. Second, verify continuity between each terminal block and its corresponding D-sub pin. Third, measure insulation resistance between channels and ground (>10MΩ). Fourth, apply a test load (preferably inductive, like a small solenoid) and verify each output switches correctly. Fifth, use an oscilloscope to verify the snubber is suppressing voltage spikes—should be noticeably cleaner than the ‘A’ revision. Sixth, run a 24-hour thermal test at 50°C ambient with all outputs at full load.

Q: What happens if a triac output fails on the TPROH1B?

A: The output may fail short or open. The enhanced snubber protection reduces the risk of failure, but triacs can still fail. If it fails short, the connected device may stay energized. If it fails open, the device won’t operate. The Mark VIe system may detect the failure through feedback monitoring. Replace the board.

Q: Is the TPROH1B hot-swappable?

A: We advise against hot-swapping power switching boards. Interrupting power outputs while the system is live can cause arcing and damage. Power down the cabinet segment before swapping.

Q: How do I verify I’m getting a genuine TPROH1B and not a remarked board?

A: Look for the additional snubber components (small RC networks) on the output paths—the ‘A’ revision lacks these. Weigh the board; the ‘B’ is slightly heavier due to the added components, about 365 grams. Look for the GE holographic security label.

Q: What’s the expected lifespan of the TPROH1B?

A: With proper cabinet cooling and clean power, these boards typically run 15-20 years. The enhanced snubber protection extends the life of the triacs when switching inductive loads. The main failure mode is typically connector wear or environmental contamination on the terminals.

Q: Where do I find the official wiring diagram for the TPROH1B?

A: GE document GEK-130542 covers the TPRO series. The H1 variant is detailed in the section specific to that configuration. The ‘B’ revision has identical terminal assignments to the ‘A’—the differences are internal. However, always cross-reference against your cabinet’s as-built drawings. Pay special attention to load ratings and wiring requirements for inductive loads. Verify every channel before terminating.

SIEMENS 6FC5371-0AA10-0AA2 PLC
GE IS220PDIOH1A
GE IS200TBCIH1C

Brand new✔ In stock ✔ Fast shipping✔
  • Email: sales@plcfcs.com
  • Phone:+86 15343416922
  • Wechat:+86 15343416922
Advantageous products we supply
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours