Description
Product Introduction
The GE IS215VCMIH1B is a VMEbus primary power supply module from the Mark VIe Speedtronic series, purpose-built to provide regulated DC power to the Mark VIe control system backplanes. This board converts the plant’s nominal 125 VDC bus (typically from battery-backed DC supplies) into the clean, regulated voltages required by processor boards, I/O modules, communication interfaces, and field devices. The H1B revision features enhanced diagnostics, predictive health monitoring, and improved efficiency.
What sets the VCMIH1B revision apart is its robust input filtering, wide input voltage tolerance (100–150 VDC), efficient operation (91% typical), enhanced diagnostics including voltage monitoring, current monitoring, temperature sensing, and predictive health monitoring. The board delivers 5 VDC at up to 25 A for logic circuits, ±12 VDC at 3 A for auxiliary circuits, and 24 VDC at 4 A for field I/O—all with low ripple for stable operation. Advanced features include input transient protection, output overvoltage and overcurrent protection, and comprehensive status monitoring. For system integrators requiring a reliable, high-performance primary power solution with advanced diagnostics for Mark VIe systems, this board is the direct OEM solution.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input Voltage | 125 VDC nominal (range: 100–150 VDC) |
| Input Current | 3.9 A typical at full load |
| Output 1 (Logic) | 5 VDC @ 25 A continuous, 30 A peak |
| Output 2 (Auxiliary) | +12 VDC @ 3 A continuous |
| Output 3 (Auxiliary) | −12 VDC @ 3 A continuous |
| Output 4 (Field) | 24 VDC @ 4 A continuous, 5 A peak |
| Output Ripple | <30 mV peak-to-peak at full load (all outputs) |
| Efficiency | 91% typical at 125 VDC input, full load |
| Isolation | 2,500 VDC input-to-output |
| Overvoltage Protection | 5.5 V clamp (5 V), 13.5 V clamp (±12 V), 28 V clamp (24 V) |
| Overcurrent Protection | Foldback current limiting, auto-recovery |
| Input Transient Protection | 1,500 V surge withstand, 100 µs |
| Status Monitoring | Voltage, current, temperature, health |
| Predictive Health Indicators | Capacitor aging estimation |
| Operating Temperature | 0 to +55°C (ambient), derated above 50°C |
| Storage Temperature | −40 to +85°C |
| Form Factor | 6U VME, single slot |
| Connectors | P1/P2 VME backplane, front panel terminal block |
| Power Draw | 125 VDC @ 3.9 A typical (487 W input) |
| Firmware | Requires Mark VIe Toolkit v6.5 or higher |
Key Selling Points & Differentiators
- High Current Capacity: 25 A on 5 V rail—supports heavily loaded backplanes with multiple processor and I/O boards.
- Multiple Output Rails: 5 V, ±12 V, and 24 V outputs—supplies all Mark VIe backplane power requirements from a single module.
- High Efficiency: 91% efficiency—reduces heat generation and improves reliability in tightly packed cabinets.
- Enhanced Diagnostics: Voltage, current, temperature, and health monitoring with predictive indicators.
- Predictive Health Monitoring: Capacitor aging estimation enables proactive maintenance planning.
- Comprehensive Protection: Foldback current limiting, overvoltage clamping, and thermal shutdown.
- Wide Input Range: Accepts 100–150 VDC, covering typical plant battery voltages and fluctuations.
- Live Test Verified: Every board undergoes a 48-hour burn-in at full rated load with cycling input voltage. We log output voltages, ripple, thermal performance, and diagnostic thresholds.
- 90-Day Warranty: Covers functional defects. If it fails under normal operating conditions, we replace it. No restocking fee for verified returns.
- OEM Traceability: All units come from audited surplus channels with original GE anti-static bags and serialized labels. No clones, no refurbished units with unknown repair history.
- Pre-Shipment Capacitor Reform: For units stored more than 12 months, we perform controlled capacitor reforming to prevent inrush failures.
Frequently Asked Questions (FAQ)
Q: What is the difference between IS215VCMIH1B and IS215PCMIH1A?
A: Both boards provide primary power with similar specifications. The VCMIH1B and PCMIH1A are functionally similar with minor variations in firmware compatibility. Verify with your existing system before replacing. In most cases, they are interchangeable.
Q: What is the difference between IS215VCMIH1B and IS215VCMIH1A?
A: The H1B revision typically includes enhanced diagnostics and predictive health monitoring over H1A. If you have H1A, verify compatibility. In most cases, H1A and H1B are interchangeable, but confirm with the board’s firmware requirements.
Q: What is the predictive health monitoring feature?
A: The VCMIH1B continuously monitors capacitor aging and estimates remaining capacitor life based on temperature and operating hours. This enables proactive maintenance planning—you can replace the power supply during scheduled maintenance rather than reacting to unexpected failure. The health status is reported through the Mark VIe Toolkit.
Q: What is the benefit of the 91% efficiency?
A: Higher efficiency means less heat generation inside the cabinet. For a 487 W power supply, 91% efficiency generates approximately 44 W of heat vs. 49 W for an 89% efficient supply. This difference can impact cabinet temperature and component life in tightly packed cabinets.
Q: Can I use this board with 24 VDC or 48 VDC input instead of 125 VDC?
A: No. The VCMIH1B is specifically designed for 125 VDC nominal input (100–150 VDC range). Using lower voltages will not produce the required outputs—the converter needs at least 90 VDC to regulate properly. Using higher voltages (above 150 VDC) will damage the input stage.
Q: Is this board hot-swappable?
A: No. The Mark VIe VME backplane does not support live insertion of power boards. You must de-energize the entire rack, wait for all LEDs to extinguish, and discharge the input bus capacitors (use a resistor, not a short). We’ve seen technicians try to pull a VCMI with the rack still powered—it arced across the backplane pins and took out neighboring boards. Don’t risk it.
Q: What is the typical lead time for this part?
A: We stock these on the shelf—usually ship within 24 hours. For international orders, add 3–5 days for customs. If you need expedited (overnight air), coordinate with our logistics team.
Q: Does this board work with both Mark VIe and Mark VIeS (SIL-rated) cabinets?
A: Yes—with a caveat. SIL systems typically require redundant power supplies (two VCMI boards in parallel with diode isolation). The H1B can be used in those configurations, but you must ensure your backplane supports the OR-ing diodes. If your SIL system uses IS220VCMI variants, check the diode configuration first. We can help verify compatibility.
Q: What’s your return policy if this doesn’t fix my power-related fault?
A: If the board is electrically functional (passes our QC test) but doesn’t clear your fault, we’ll accept a return within 30 days provided the board shows no physical damage, no blown fuses, and no signs of overvoltage stress. We do charge a 15% restocking fee if the fault was due to a downstream short circuit or incorrect input voltage. We’ll work with you over the phone to diagnose the issue before we ship—our goal is to get you running, not to ship boxes back and forth.

IS200 VSCA
IS200 VSCAH MARK VI CARD
IS200 VSCAH2A MARK VI CARD
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922