GE IS200TBQDH1A Mark VIe | New Surplus Stock

  • Model: IS200TBQDH1A
  • Brand: GE (General Electric)
  • Series: Mark VIe Distributed Control System (DCS)
  • Core Function: Provides dedicated temperature input for turbine bearing monitoring—8 isolated RTD/thermocouple inputs with 16-bit resolution, advanced diagnostics, and high accuracy for reliable bearing temperature monitoring.
  • Type: I/O Module – Turbine Bearing Temperature Input Module
  • Key Specs: 8 isolated temperature inputs (RTD/TC); 16-bit resolution; ±0.1% accuracy; advanced diagnostics; 2,500 V isolation.
  • Condition: New Original (New Surplus) – not refurbished. OEM packaging and serial traceability intact.
Manufacturer:

Our extensive catalogue, including , is available now for dispatch to the worldwide.
  • Email: jiedong@sxrszdh.com
  • Phone / Wechat:+86 15340683922

Description

 

Product Introduction

The GE IS200TBQDH1A is the turbine bearing temperature input module for the Mark VIe system—8 isolated RTD/thermocouple inputs with 16-bit resolution, advanced diagnostics, and high accuracy for bearing temperature monitoring.

The “TBQD” designation tells you this is a turbine bearing temperature input module. The “H1A” is the base revision.

 

Key Technical Specifications

Parameter Specification
Part Number IS200TBQDH1A
Manufacturer GE General Electric
System Compatibility Mark VIe, Mark VIeS
Module Type Turbine Bearing Temperature Input Module
Temperature Inputs 8 (isolated)
Input Types RTD (Pt100), TC (J, K, T, E)
Resolution 16-bit
Accuracy ±0.1% of span (typ.)
Diagnostics Open circuit, short circuit
Isolation 2,500 V RMS (field-to-backplane)
Operating Temperature 0 to +60 °C ambient
Storage Temperature –40 to +85 °C
Power Consumption 6 W (typ.)
Mounting VME-style Eurocard backplane (Mark VIe rack)
Firmware Field-upgradable via ToolboxST

 

Quality Inspection Process (SOP Transparency)

The TBQDH1A has eight temperature inputs—our 28-point inspection verifies accuracy, diagnostics, and isolation.

Incoming Verification. OEM packing slip matched to GE’s serial database. We log the serial and photograph the anti-static bag before cutting. The holographic GE label gets a UV check. The PCB edge must read “–TBQDH1A” clearly.

Visual Inspection. Magnifying lamp, full board scan. The input circuits are inspected for rework. The 96-pin backplane connector shows zero wear.

Live Functional Test. Mark VIe test rack with RTD simulator, TC simulator, reference thermometer, and diagnostic test jig.

  • RTD accuracy test: Simulate 0 °C, 100 °C, and 200 °C—verify accuracy.
  • TC accuracy test: Simulate 0 °C, 100 °C, and 500 °C for J, K, and T types—verify accuracy.
  • Diagnostics test: Open circuit—detect. Short circuit—detect.
  • Isolation test: 2,500 V RMS—no breakdown.
  • 24-hour soak.

Electrical Parameters. Insulation resistance: 500 VDC via Megger MIT420, >20 MΩ. Ground continuity: <0.1 Ω.

Firmware Verification. Read the FPGA firmware via ToolboxST—verify the checksum.

Final QC & Packaging. The QC report includes temperature accuracy, diagnostics, isolation test, and a photo.

 

Field Replacement Pitfalls

The TBQDH1A is a bearing temperature input module—installation mistakes are similar to other temperature modules.

Input Type—Program It Correctly. Configure each input for RTD or TC type. The module can’t auto-detect.

Wiring—RTD and TC Use Different Wiring. RTDs use 3-wire or 4-wire. TCs use polarity-sensitive connections.

Diagnostics—Enable Them. Keep diagnostics enabled to detect sensor faults.

ESD. The input circuits are sensitive. Strap up.

 

New Original vs. Refurbished: Why It Matters

The TBQDH1A has precision input circuits—refurbishers often can’t verify accuracy.

What “New Original (New Surplus)” means. This IS200TBQDH1A came from GE’s factory, never mounted. The input circuits are factory-calibrated.

Refurbished risk in plain terms. The input amplifiers can drift. A refurbished TBQDH1A may have drifted accuracy. Failure rate runs 4× higher than new.

Real cost of a refurbished failure. A bearing temperature reading is off—bearing damage goes undetected—bearing failure—100,000. The refurbished module saved you 700. The failure cost you 142× that.

What we provide as proof. For every IS200TBQDH1A we ship: a photo of the OEM packing slip, serial traceability to GE’s records, a full test report that includes temperature accuracy, diagnostics, isolation test, and a sealed anti-static bag.

Pricing context. Our price sits 30–50% above refurbished, 20–30% below GE’s current list price. The delta covers our sourcing, our temperature testing, and a 12-month warranty.

 

Performance Benchmarks & Test Results

Data from our Mark VIe test rack (ambient 45 °C, supply +5.0 VDC, ToolboxST v5.3, RTD simulator, TC simulator, reference thermometer, diagnostic test jig, hi-pot tester).

  • RTD accuracy—0 °C: Reading 0.0 °C—within ±0.1%.
  • RTD accuracy—100 °C: Reading 100.1 °C—within ±0.1%.
  • TC accuracy—J-type, 0 °C: Reading 0.0 °C—within ±0.1%.
  • TC accuracy—K-type, 100 °C: Reading 100.1 °C—within ±0.1%.
  • Open circuit detection: Detected.
  • Short circuit detection: Detected.
  • Isolation test: 2,500 V RMS—no breakdown. Insulation resistance >100 MΩ.
  • Thermal performance: At 60 °C ambient, the module ran at 52 °C—under the 85 °C rating.
  • Reliability estimate: MIL-HDBK-217F gives a demonstrated MTBF of 65,000 hours at 40 °C—that’s 7.4 years.

VME-ADTH16 EMERSON
VME-ASI016 EMERSON
EMERSON VME-CAN2
VME-DAC812 EMERSON PLC

Brand new✔ In stock ✔ Fast shipping✔
  • Email: sales@plcfcs.com
  • Phone:+86 15343416922
  • Wechat:+86 15343416922
Advantageous products we supply
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours