Description
Product Introduction
The GE DS3800HRDA1C1C is a fully populated I/O link card from the Mark VI Speedtronic series, combining factory-configured Type K thermocouple input scaling with high-performance signal conditioning, precision components, and internal IONet termination. This variant is specifically engineered for critical turbine exhaust gas temperature monitoring applications requiring the highest measurement accuracy and simplified end-of-chain installation.
What distinguishes the 1C1C suffix is its factory-set uniform configuration that enables Type K thermocouple operation with cold-junction compensation on all eight analog channels, with the ‘A’ base model providing internal termination. This specialized board is ideal for gas turbine installations requiring high-accuracy temperature monitoring at end-of-chain positions. We stock verified units with logged firmware versions and complete test records. No rework, no counterfeit—just OEM-spec hardware ready for deployment.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input Voltage | 24 VDC ±10% (nominal) |
| Discrete Inputs | 16 optically isolated, 24 V sink/source |
| Discrete Outputs | 16 solid-state, 0.5 A per channel max |
| Thermocouple Inputs | 8 channels, factory-configured for Type K (all channels) |
| Thermocouple Range | Type K: –200°C to +1,200°C (–328°F to +2,192°F) |
| Cold-Junction Compensation | Onboard sensor, ±0.5°C accuracy, factory-calibrated |
| Analog Input Impedance | > 10 MΩ (differential) |
| Analog Input Accuracy | ±0.05% of full scale at 25°C |
| Analog Input Accuracy (temperature) | ±0.1% of full scale (0°C to +60°C) |
| Analog Input Resolution | 12-bit (4096 counts) |
| Common-Mode Rejection | > 100 dB at 50/60 Hz |
| Input Noise | < 2 µV RMS (typical) |
| Gain Accuracy | ±0.05% of reading |
| Input Filtering | Standard filtering |
| IONet Termination | Internal 120 Ω resistor (factory-enabled) |
| Analog Outputs | 2 channels, 0-20 mA or 0-10 V (jumper-selectable) |
| Communication Protocol | GE IONet (proprietary, 2 Mbps) |
| Isolation Voltage | 1500 VAC (field-to-logic) |
| Operating Temperature | 0°C to +60°C (32°F to 140°F) |
| Storage Temperature | –40°C to +85°C |
| Humidity | 5% to 95% non-condensing |
| Power Consumption | 7.2 W typical |
| Dimensions | 18.5 cm x 12.7 cm x 3.0 cm (std. Mark VI form factor) |
Key Selling Points & Differentiators
- High-Performance Thermocouple Measurement: Precision components and low-drift amplifiers deliver ±0.05% accuracy for critical turbine exhaust temperature monitoring.
- Eight Type K Channels: All eight analog inputs dedicated to Type K thermocouples with onboard CJC—eliminates external transmitters and signal conditioners.
- Built-In IONet Termination: Internal 120 Ω resistor factory-enabled—eliminates the need for external terminators on end-of-chain installations.
- Temperature-Stable Accuracy: ±0.1% full scale across the entire 0°C to +60°C operating range—minimal temperature-related drift.
- Factory-Configured Inputs: Pre-configured Type K scaling and CJC optimized for exhaust gas monitoring—saves field commissioning time.
- Full Factory Test: Every unit undergoes a 24-hour burn-in with live I/O loopback, precision microvolt source calibration (spanning Type K range), CJC verification, and communication handshake verification—includes signed QC report with measured values for all channels.
- 30-Day Compatibility Guarantee: If the module does not function in your specific firmware revision (we log the onboard firmware), return for full credit—no restocking fee.
- Anti-Counterfeit Sealed: Each DS3800HRDA1C1C ships with tamper-evident packaging and visual inspection photos taken at receipt.
- Cost-Effective Alternative: Priced 45-60% below GE’s new MSRP while maintaining OEM-spec performance through live testing.
Frequently Asked Questions (FAQ)
Can I hot-swap the DS3800HRDA1C1C while the turbine is running?
No—absolutely not. The Mark VI backplane does not support live insertion for this module. You will need a full shutdown and power cycle. In our experience, attempting hot-swap can corrupt the IONet sync and force a controller reset. Always isolate the rack before removal.
What exactly does the 1C1C suffix mean, and does it matter for my application?
Yes, the suffix is critical. Both ‘C’ suffixes indicate Type K thermocouple configuration on all eight analog channels with CJC enabled. The ‘A’ base model provides internal termination. If your temperature sensors are Type J or T, you’ll need to select a different variant. If this board sits in the middle of the IONet network, its internal termination would cause double-termination—this variant should only be used at end positions.
What makes this board different from the DS3800HRCA1C1C?
Both boards provide the same Type K thermocouple configuration, high-performance components, standard filtering, and internal termination. The difference is in the base model suffix—’D’ versus ‘C’—which may indicate different factory configurations, component selections, or calibration tolerances. In practical terms, they are functionally identical. If you need specific revision or date code information, we can check our stock.
What makes this board different from the DS3800HRDA1C1B?
The HRDA1C1C has uniform Type K thermocouple configuration on all eight channels, while the HRDA1C1B has Type K thermocouples on channels 1-4 and PT100 RTDs on channels 5-8. Both boards provide high-performance components, standard filtering, and internal termination. Choose based on your sensor types—all thermocouple versus mixed thermocouple and RTD.
How do I verify if this board matches my existing firmware revision?
We log the firmware version from every unit during our inbound test. Before shipping, we can confirm whether it matches your current revision. This is particularly important because the precision calibration constants, CJC calibration data, and linearization tables reside in onboard memory. A mismatch can cause a +1.5°C offset at 1,000°C. If it differs, we advise updating your controller or request a specific rev from our stock.
These are surplus units—how do I know they aren’t counterfeit or repaired?
We maintain full traceability: every DS3800HRDA1C1C is photographed upon receipt, cross-checked against GE’s OEM marking guide (including board revision, date code, and component-level verification), and tested for electrical characteristics (insulation > 10 MΩ, current draw within 5% of spec). We do not sell repaired boards—only clean, functional pulls or new surplus. The QC tag includes our test signature and a photo record of the board’s condition.
What happens if the board fails after installation?
Our standard warranty covers functional defects for 12 months from shipment. That said, we do not cover damage from ESD, incorrect wiring, or overvoltage. To be frank, high-performance thermocouple boards like the HRDA1C1C are more sensitive to ESD and thermal gradients—we recommend proper grounding and handling procedures, and avoiding mounting the board near heat sources or in areas with rapid temperature changes. For thermocouple inputs, use shielded extension wire and ground the shield only at the source end.
Is programming or configuration required, or is it plug-and-play?
It’s “plug-and-play” only if your IONet configuration already expects an HRDA1C1C at that slot address and your field sensors are all Type K thermocouples. Otherwise, you must reconfigure the I/O map in the CIMPLICITY or Toolbox software to match the board’s factory scaling. The board stores no user program—all logic resides in the controller. You will not lose turbine sequences by swapping this board.
What shipping and packaging precautions do you take?
Each board is placed in an anti-static bag, wrapped in ESD foam, and double-boxed with desiccant. High-performance thermocouple cards with precision CJC sensors are sensitive to moisture, contamination, and thermal shock—we seal the inner bag with a tamper-evident label, include a humidity indicator card, and use anti-corrosion packaging. We’ve shipped to offshore platforms, desert installations, and Arctic sites without humidity-related failures. If you need expedited customs documentation, we include commercial invoices with Harmonized Code 8538.90.8160.

GE IS220PAICH1B
GE IC693PWR322LT
GE IC693PWR322E
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922