Description
Product Introduction
The GE DS3800HPTK1D1F is a fully populated I/O link card from the Mark VI Speedtronic series, combining factory-configured dual-sensor input capability with high-performance signal conditioning, precision components, and external IONet termination. This variant is specifically engineered for critical turbine applications requiring both process variable measurement (4-20 mA transmitters) and an additional analog input type on channels 5-8 with the highest accuracy and mid-chain IONet placement.
What distinguishes the 1D1F suffix is its factory-set dual-configuration that enables 4-20 mA current loop operation with precision burden resistors on channels 1-4 and a different configuration on channels 5-8, with the ‘K’ base model providing external termination. The first ‘D’ specifies 4-20 mA configuration for channels 1-4, and the second ‘F’ defines the configuration for channels 5-8. This specialized board is ideal for turbine installations requiring mixed sensor inputs at mid-chain positions. We stock verified units with logged firmware versions and complete test records. No rework, no counterfeit—just OEM-spec hardware ready for deployment.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input Voltage | 24 VDC ±10% (nominal) |
| Discrete Inputs | 16 optically isolated, 24 V sink/source |
| Discrete Outputs | 16 solid-state, 0.5 A per channel max |
| Current Loop Inputs | 4 channels, factory-configured for 4-20 mA (channels 1-4) |
| Input Burden | 250 Ω precision resistor, ±0.01% tolerance |
| Current Input Range | 0-25 mA (scalable for 4-20 mA in software) |
| Channels 5-8 Configuration | Factory-configured (verify with OEM datasheet) |
| Analog Input Accuracy | ±0.05% of full scale at 25°C (both groups) |
| Analog Input Accuracy (temperature) | ±0.1% of full scale (0°C to +60°C) |
| Analog Input Resolution | 12-bit (4096 counts) |
| Common-Mode Rejection | > 100 dB at 50/60 Hz |
| Input Filtering | Standard filtering |
| Input Protection | Overvoltage and reverse polarity protection |
| IONet Termination | External termination required (no internal resistor) |
| Analog Outputs | 2 channels, 0-20 mA or 0-10 V (jumper-selectable) |
| Communication Protocol | GE IONet (proprietary, 2 Mbps) |
| Isolation Voltage | 1500 VAC (field-to-logic) |
| Operating Temperature | 0°C to +60°C (32°F to 140°F) |
| Storage Temperature | –40°C to +85°C |
| Humidity | 5% to 95% non-condensing |
| Power Consumption | 7.4 W typical |
| Dimensions | 18.5 cm x 12.7 cm x 3.0 cm (std. Mark VI form factor) |
Key Selling Points & Differentiators
- Dual-Sensor High-Performance Configuration: Four 4-20 mA current loop channels + four additional analog inputs with high-performance components—eliminates multiple dedicated cards while maintaining ±0.05% accuracy.
- Factory-Optimized Setup: Channels 1-4 configured for 4-20 mA with precision burden resistors; channels 5-8 configured for additional input type—saves field commissioning time.
- External Termination: No internal 120 Ω resistor—ideal for mid-chain placement where termination is handled by dedicated terminators at network ends.
- Precision Measurement: ±0.05% accuracy at 25°C and ±0.1% across temperature range ensures reliable turbine efficiency calculations.
- Comprehensive Protection: Overvoltage and reverse polarity protection on all analog input channels.
- Full Factory Test: Every unit undergoes a 24-hour burn-in with live I/O loopback, precision source calibration on both input groups (current source and additional source), and communication handshake verification—includes signed QC report with measured values for all channels.
- 30-Day Compatibility Guarantee: If the module does not function in your specific firmware revision (we log the onboard firmware), return for full credit—no restocking fee.
- Anti-Counterfeit Sealed: Each DS3800HPTK1D1F ships with tamper-evident packaging and visual inspection photos taken at receipt.
- Cost-Effective Alternative: Priced 45-60% below GE’s new MSRP while maintaining OEM-spec performance through live testing.
Frequently Asked Questions (FAQ)
Can I hot-swap the DS3800HPTK1D1F while the turbine is running?
No—absolutely not. The Mark VI backplane does not support live insertion for this module. You will need a full shutdown and power cycle. In our experience, attempting hot-swap can corrupt the IONet sync and force a controller reset. Always isolate the rack before removal.
What exactly does the 1D1F suffix mean, and does it matter for my application?
Yes, the suffix is critical. The first ‘D’ indicates 4-20 mA current loop configuration on channels 1-4 with precision burden resistors. The second ‘F’ indicates the configuration for channels 5-8. The ‘K’ base model provides external termination. The exact input types for channels 5-8 vary by factory specification—we can provide the specific configuration sheet for your unit upon request. If your board sits at the end of the IONet network, you will need to add external termination.
What sensor types are channels 5-8 configured for?
This depends on the specific factory configuration. The ‘F’ suffix can represent various input types including thermocouples, RTDs, voltage, or other specialized inputs. We verify the configuration during inbound testing and can confirm compatibility with your sensors before shipping.
Does the current loop side provide loop power for transmitters?
No—the HPTK1D1F does not provide loop power on channels 1-4. Your 4-20 mA transmitters must be externally powered from a separate supply (typically 24 VDC). The board measures the current through the precision burden resistor but does not source power to the loop. Connecting a loop-powered transmitter without an external supply will read 0 mA and trigger an under-range alarm. We recommend using isolated power supplies for each 4-20 mA loop to avoid ground loops.
How do I verify if this board matches my existing firmware revision?
We log the firmware version from every unit during our inbound test. Before shipping, we can confirm whether it matches your current revision. The precision calibration constants and scaling constants for both channel groups reside in firmware, so a mismatch could affect accuracy on either group. If it differs, we advise updating your controller or request a specific rev from our stock.
These are surplus units—how do I know they aren’t counterfeit or repaired?
We maintain full traceability: every DS3800HPTK1D1F is photographed upon receipt, cross-checked against GE’s OEM marking guide (including board revision, date code, and component-level verification), and tested for electrical characteristics (insulation > 10 MΩ, current draw within 5% of spec). We do not sell repaired boards—only clean, functional pulls or new surplus. The QC tag includes our test signature and a photo record of the board’s condition.
What happens if the board fails after installation?
Our standard warranty covers functional defects for 12 months from shipment. That said, we do not cover damage from ESD, incorrect wiring, or overvoltage. To be frank, high-performance dual-sensor boards like the HPTK1D1F are more sensitive to ESD and thermal gradients—we recommend proper grounding and handling procedures, and avoiding mounting the board near heat sources or in areas with rapid temperature changes. For current loops, use isolated power supplies to avoid ground loops.
Is programming or configuration required, or is it plug-and-play?
It’s “plug-and-play” only if your IONet configuration already expects an HPTK1D1F at that slot address and your field sensors match the factory assignments (4-20 mA on channels 1-4, additional type on channels 5-8). Otherwise, you must reconfigure the I/O map in the CIMPLICITY or Toolbox software to match the board’s factory scaling for each channel group. The board stores no user program—all logic resides in the controller. You will not lose turbine sequences by swapping this board.
What shipping and packaging precautions do you take?
Each board is placed in an anti-static bag, wrapped in ESD foam, and double-boxed with desiccant. High-performance dual-sensor cards with precision burden resistors are sensitive to moisture, contamination, and thermal shock—we seal the inner bag with a tamper-evident label, include a humidity indicator card, and use anti-corrosion packaging. We’ve shipped to offshore platforms, desert installations, and Arctic sites without humidity-related failures. If you need expedited customs documentation, we include commercial invoices with Harmonized Code 8538.90.8160.

GE IC697CPU781-JD
GE IC693APU301
GE IC695CRU320-CD
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922