Description
Product Introduction
The GE DS3800HPLA1A1A is a fully populated I/O link card from the Mark VI Speedtronic series, combining factory-configured Type J thermocouple input scaling with high-performance signal conditioning, precision components, and external IONet termination. This variant is specifically engineered for critical turbine exhaust gas temperature monitoring applications requiring the highest measurement accuracy and mid-chain IONet placement.
What distinguishes the 1A1A suffix is its factory-set uniform configuration that enables Type J thermocouple operation with cold-junction compensation on all eight analog channels, with the ‘A’ base model providing external termination. This specialized board is ideal for turbine installations requiring high-accuracy temperature monitoring at mid-chain positions. We stock verified units with logged firmware versions and complete test records. No rework, no counterfeit—just OEM-spec hardware ready for deployment.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input Voltage | 24 VDC ±10% (nominal) |
| Discrete Inputs | 16 optically isolated, 24 V sink/source |
| Discrete Outputs | 16 solid-state, 0.5 A per channel max |
| Thermocouple Inputs | 8 channels, factory-configured for Type J (all channels) |
| Thermocouple Range | Type J: –40°C to +760°C (–40°F to +1,400°F) |
| Cold-Junction Compensation | Onboard sensor, ±0.5°C accuracy, factory-calibrated |
| Analog Input Impedance | > 10 MΩ (differential) |
| Analog Input Accuracy | ±0.05% of full scale at 25°C |
| Analog Input Accuracy (temperature) | ±0.1% of full scale (0°C to +60°C) |
| Analog Input Resolution | 12-bit (4096 counts) |
| Common-Mode Rejection | > 100 dB at 50/60 Hz |
| Input Noise | < 2 µV RMS (typical) |
| Gain Accuracy | ±0.05% of reading |
| Input Filtering | Standard filtering |
| IONet Termination | External termination required (no internal resistor) |
| Analog Outputs | 2 channels, 0-20 mA or 0-10 V (jumper-selectable) |
| Communication Protocol | GE IONet (proprietary, 2 Mbps) |
| Isolation Voltage | 1500 VAC (field-to-logic) |
| Operating Temperature | 0°C to +60°C (32°F to 140°F) |
| Storage Temperature | –40°C to +85°C |
| Humidity | 5% to 95% non-condensing |
| Power Consumption | 7.2 W typical |
| Dimensions | 18.5 cm x 12.7 cm x 3.0 cm (std. Mark VI form factor) |
Key Selling Points & Differentiators
- High-Performance Thermocouple Measurement: Precision components and low-drift amplifiers deliver ±0.05% accuracy for critical turbine exhaust temperature monitoring.
- Eight Type J Channels: All eight analog inputs dedicated to Type J thermocouples with onboard CJC—eliminates external transmitters and signal conditioners.
- External Termination: No internal 120 Ω resistor—ideal for mid-chain placement where termination is handled by dedicated terminators at network ends.
- Temperature-Stable Accuracy: ±0.1% full scale across the entire 0°C to +60°C operating range—minimal temperature-related drift.
- Factory-Configured Inputs: Pre-configured Type J scaling and CJC optimized for exhaust gas monitoring—saves field commissioning time.
- Full Factory Test: Every unit undergoes a 24-hour burn-in with live I/O loopback, precision microvolt source calibration (spanning Type J range), CJC verification, and communication handshake verification—includes signed QC report with measured values for all channels.
- 30-Day Compatibility Guarantee: If the module does not function in your specific firmware revision (we log the onboard firmware), return for full credit—no restocking fee.
- Anti-Counterfeit Sealed: Each DS3800HPLA1A1A ships with tamper-evident packaging and visual inspection photos taken at receipt.
- Cost-Effective Alternative: Priced 45-60% below GE’s new MSRP while maintaining OEM-spec performance through live testing.
Frequently Asked Questions (FAQ)
Can I hot-swap the DS3800HPLA1A1A while the turbine is running?
No—absolutely not. The Mark VI backplane does not support live insertion for this module. You will need a full shutdown and power cycle. In our experience, attempting hot-swap can corrupt the IONet sync and force a controller reset. Always isolate the rack before removal.
What exactly does the 1A1A suffix mean, and does it matter for my application?
Yes, the suffix is critical. Both ‘A’ suffixes indicate Type J thermocouple configuration on all eight analog channels with CJC enabled. The ‘A’ base model provides external termination. If your temperature sensors are Type K or T, you’ll need to select a different variant. If your board sits at the end of the IONet network, you will need to add external termination.
What makes this board different from the DS3800HPBC1A1A?
The HPLA1A1A has external IONet termination required (‘A’ suffix), while the HPBC1A1A has internal termination active. Both boards provide the same Type J thermocouple configuration, high-performance components, and standard filtering. For mid-chain installations, the HPLA1A1A is the right choice. For end-of-chain placement, use the HPBC1A1A.
What makes this board different from the DS3800HMPG1A1A?
The HPLA1A1A provides standard filtering and external termination. The HMPG1A1A provides advanced filtering (50/60 Hz notch filters), comprehensive diagnostics, and internal termination. For applications in electrically noisy environments requiring advanced noise rejection and diagnostic feedback with end-of-chain placement, the HMPG series is the preferred choice. For standard applications with mid-chain placement, the HPLA series provides excellent performance at a lower cost point.
How do I verify if this board matches my existing firmware revision?
We log the firmware version from every unit during our inbound test. Before shipping, we can confirm whether it matches your current revision. This is particularly important because the precision calibration constants, CJC calibration data, and linearization tables reside in onboard memory. A mismatch can cause a +1.2°C offset at 700°C. If it differs, we advise updating your controller or request a specific rev from our stock.
These are surplus units—how do I know they aren’t counterfeit or repaired?
We maintain full traceability: every DS3800HPLA1A1A is photographed upon receipt, cross-checked against GE’s OEM marking guide (including board revision, date code, and component-level verification), and tested for electrical characteristics (insulation > 10 MΩ, current draw within 5% of spec). We do not sell repaired boards—only clean, functional pulls or new surplus. The QC tag includes our test signature and a photo record of the board’s condition.
What happens if the board fails after installation?
Our standard warranty covers functional defects for 12 months from shipment. That said, we do not cover damage from ESD, incorrect wiring, or overvoltage. To be frank, high-performance thermocouple boards like the HPLA1A1A are more sensitive to ESD and thermal gradients—we recommend proper grounding and handling procedures, and avoiding mounting the board near heat sources or in areas with rapid temperature changes. For thermocouple inputs, use shielded extension wire and ground the shield only at the source end.
Is programming or configuration required, or is it plug-and-play?
It’s “plug-and-play” only if your IONet configuration already expects an HPLA1A1A at that slot address and your field sensors are all Type J thermocouples. Otherwise, you must reconfigure the I/O map in the CIMPLICITY or Toolbox software to match the board’s factory scaling. The board stores no user program—all logic resides in the controller. You will not lose turbine sequences by swapping this board.
What shipping and packaging precautions do you take?
Each board is placed in an anti-static bag, wrapped in ESD foam, and double-boxed with desiccant. High-performance thermocouple cards with precision CJC sensors are sensitive to moisture, contamination, and thermal shock—we seal the inner bag with a tamper-evident label, include a humidity indicator card, and use anti-corrosion packaging. We’ve shipped to offshore platforms, desert installations, and Arctic sites without humidity-related failures. If you need expedited customs documentation, we include commercial invoices with Harmonized Code 8538.90.8160.

GE IS210DTCIH1AA
GE IS210DTRTH1AA
GE IS210DTTCH1AA
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922