Description

Product Introduction
The GE DS3820PSLB is a primary power conversion board for the Speedtronic Mark V turbine control system. This module mounts directly into the Mark V rack and accepts a nominal 125 VDC input from the plant’s battery-backed DC bus, generating the isolated, regulated DC voltages required by CPU, I/O, and communication cards in the chassis.
What sets this PSLB revision apart is its improved filtering on the 125 VDC input and tighter regulation on the +5 VDC rail, critical for stable operation of processor-heavy Mark V configurations. For facilities maintaining legacy gas or steam turbine controls, this board is a direct drop-in replacement for earlier PSLx variants, with identical footprint and pinout. We stock tested units that let you avoid the 6-8 week lead times typical of repair loops.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | GE (General Electric) |
| Model Number | DS3820PSLB |
| Series | Speedtronic Mark V |
| Input Voltage | 125 VDC nominal (100-140 VDC range) |
| Output Voltages | +5 VDC @ 5A, +15 VDC @ 1A, -15 VDC @ 0.5A |
| Total Output Power | 50W maximum |
| Isolation Rating | 1500 VDC (input-to-output) |
| Operating Temperature | 0 to +60°C (ambient, forced air required) |
| Storage Temperature | -40 to +85°C |
| Dimensions | 8.5″ x 4.2″ x 1.5″ (standard Mark V 1-slot width) |
| Connector | 96-pin DIN 41612 (Type C) |
| Mounting | Rack backplane, horizontal orientation |
| Indicators | Single green LED per output rail (present/absent) |
Key Selling Points & Differentiators
- Drop-in replacement for PSLB/PSLA variants. No wiring changes, bracket modifications, or backplane adapter cards. Match your old unit’s physical dimensions and connector exactly.
- Rigorous 48-hour burn-in test. Every unit runs at 125 VDC with a 50% dummy load (25W) for two full days, with output ripple monitored below 50 mV peak-to-peak on the critical +5V rail. We log thermal cycling from 25°C to 50°C.
- Full firmware/config independence. This is an analog power converter—no firmware version mismatches, no config file transfers, no lost programming. Swap and power up.
- ESD-protected packaging. Anti-static bag, foam-lined box, and desiccant included. We ship with wrist strap and ESD warning label on the outer carton.
- 18-month warranty covering output voltage tolerance (±3%) and load regulation. If it fails under specified conditions, we cross-ship a replacement within 24 hours.
- Contrast with repairs: Avoid the common failure point of repaired boards using non-OEM capacitors. Our surplus units carry original GE components from the same production batch as the last OEM run (2012-2014). Verified with GE factory test reports on request.
Frequently Asked Questions (FAQ)
Q: Can I hot-swap this DS3820PSLB while the Mark V is running?
A: To be frank—no, and we don’t recommend it. The 125 VDC input section has large bulk capacitors that charge instantly on insertion, causing a current spike that can trip the upstream DC breaker or glitch adjacent cards. Always power down the chassis, wait 30 seconds for bus caps to discharge, then replace. In our experience, hot-swapping is the #1 cause of connector pin damage on these 96-pin DINs.
Q: This will directly replace my existing DS3820PSLA, right?
A: Yes, mechanically and electrically. The “B” revision added a ferrite bead on the +15 V output to reduce high-frequency noise for analog servo cards. Your chassis will not care—it’s a passive component change. The pinout, mounting holes, and voltage set points are identical. No dip switch or jumper changes required.
Q: How do I know these surplus boards are genuine GE and not counterfeit?
A: Valid question. We log every unit’s serial number against GE’s final production manifests from 2014. We also check the PCB substrate color (dark green, not light green or yellow), the GE logo silk-screen quality, and the date codes on the main transformer and input rectifier. If any of those fail our inbound check, we reject the batch. We’ll provide a photo of your specific board’s top and bottom layers before shipping if requested.
Q: What happens if the board fails during the warranty period and I’m in a plant outage?
A: We keep at least three tested PSLB units on the shelf at all times for exactly this scenario. You call our 24/7 support line, we verify the failure symptoms (we’ll walk you through output voltage measurements at the backplane), and if confirmed, we overnight a replacement. You ship the failed one back within 30 days. No repair depot wait times, no troubleshooting fees.
Q: Will this board work with a 110 VDC nominal input instead of 125 VDC?
A: Yes, but with a caveat. The undervoltage lockout trips at about 95 VDC. At 110 VDC, you’re within the 100-140V range, but the +5 V output will run at about 4.85 V under full load, which is still within GE’s ±5% tolerance (4.75-5.25V). If your bus dips below 100V during startup, the board will shut down and auto-recover when voltage comes back. We recommend measuring your actual bus voltage at the rack with a Fluke 87V—we’ve seen plant batteries at 108 VDC cause intermittent resets that look like CPU faults.
Q: Does this come with the mating backplane connector or terminal block?
A: No—the DS3820PSLB plugs directly into the Mark V backplane via its 96-pin DIN connector, which is part of the chassis, not the board. There are no field-wiring terminals on this module. All input power and output distribution goes through the backplane. If your backplane pins are damaged (bent or corroded), we can supply a replacement backplane section separately—just ask.
Q: Can you ship this internationally, and do you handle customs documentation?
A: Yes, we ship to over 40 countries. We export as “industrial electronic parts – power supply board” with HS code 8504.40.70. We include a commercial invoice, packing list, and (for some countries) a certificate of origin. That said, you are responsible for any import duties or customs clearance delays. We’ve had shipments to Brazil held for 3 weeks, so if you need it urgently, use DHL Express and we’ll handle the brokerage on our end.
GE IC695CPE310
DEIF LSU-113DG
ABB PPC902AE101 3BHE010751R0101
REXROTH MKD071B-061-KG1-KN
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922