Description
Product Introduction
The GE DS3815PFCA is a power supply module for the Mark VI Speedtronic turbine control rack, configured for 240 VAC input with extended temperature capability. This IS200-series PSU converts a standard 240 VAC single-phase supply into the regulated DC voltages required by the CPU, I/O boards, and backplane. It is the AC-input equivalent of the DS3815PCPA (which accepts 125 VDC), sharing the same 250W output capacity and extended -40 to +75°C temperature range.
The DS3815PFCA provides three output rails: 48 VDC for the CPU bus, 24 VDC for field device loop power, and 5 VDC for logic-level circuits. Total output capacity is 250W with standard filtering (<50 mV on 5V rail). The F in the suffix indicates 240 VAC input. The C indicates extended temperature rating (-40 to +75°C). This is the AC-powered PSU for high-temperature installations where only line voltage is available—no battery bank or DC distribution required. The module includes the same backplane-specific connector as all Mark VI power supplies, sliding directly into the rack and communicating status (voltage good, overcurrent, overtemperature) to the CPU via discrete signals.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | GE (General Electric) |
| Series | Mark VI / IS200 Speedtronic |
| Model | DS3815PFCA |
| Input Voltage | 240 VAC nominal (180-264 VAC, 47-63 Hz) |
| Input Current | 1.5A max at 240 VAC (full load) |
| Input Configuration | Single-phase, L + N + Ground |
| Output 1 (CPU Bus) | 48 VDC ±5%, 4.0A (192W max) |
| Output 2 (Field Loop) | 24 VDC ±5%, 2.0A (48W max) |
| Output 3 (Logic) | 5 VDC ±3%, 2.0A (10W max) |
| Total Power Capacity | 250W continuous |
| Output Ripple & Noise (5V Rail) | <50 mV peak-to-peak |
| Output Ripple & Noise (24V/48V) | <100 mV peak-to-peak |
| Efficiency | >84% at full load |
| Hold-Up Time | 20 ms (at full load, 240 VAC input) |
| Inrush Current Limiting | Yes, soft-start circuit (NTC thermistor) |
| Protection Features | Overvoltage, overcurrent, overtemperature, input fuse (internal) |
| Status Outputs | DC OK, Overload, Overtemperature (discrete signals to CPU) |
| Cooling | Convection (no fan) |
| Operating Temperature | -40 to +75°C (derate above 65°C) |
| Storage Temperature | -40 to +85°C |
| Component Grade | Industrial extended (105°C capacitors, higher-temp semiconductors) |
| Connector Type | Backplane card-edge connector + 2 x front-panel terminal blocks |
Key Selling Points & Differentiators
- 240 VAC Input Compatibility: Direct solution for plants with standard AC power available. No DC battery bank or rectifier required. Simplifies panel design for smaller installations and retrofit projects.
- Extended Temperature Range: Rated for -40 to +75°C ambient—5°C higher than standard PFAA variants. Uses 105°C-rated capacitors and higher-grade semiconductors for hot turbine decks and un-conditioned cabinets.
- Full 250W Capacity: Sufficient for heavily populated 15-slot racks with multiple I/O modules.
- Direct Mark VI Backplane Interface: Plugs directly into the IS200 rack—same mechanical and electrical fit as other PSU variants. No configuration changes required.
- Triple Isolated Outputs: Galvanic isolation between 48V, 24V, and 5V rails prevents a fault on one rail from collapsing the others.
- Full Load Bank Test at Elevated Temperature: Every unit runs on our test rig at +75°C ambient for 24 hours, pulling full 250W load. We monitor output stability, ripple, and thermal performance. Capacitors replaced on units manufactured before 2015.
- Surplus/Refurbished with 1-Year Warranty: New surplus (original GE packaging) or professionally refurbished. 1-year warranty, 30-day return.
Frequently Asked Questions (FAQ)
Q: What’s the difference between DS3815PFCA and DS3815PAAA?
Input type and temperature rating. The PFCA accepts 240 VAC input and has extended temperature rating (-40 to +75°C). The PAAA accepts 125 VDC input (or 240 VAC in some variants) and has standard temperature rating (-40 to +70°C). Both deliver 250W with standard filtering. The PFCA is the AC-powered version for high-temperature installations. The PAAA is the DC-powered (or AC/DC) standard version.
Q: What’s the difference between DS3815PFCA and DS3815PCPA?
Input type. The PFCA accepts 240 VAC input. The PCPA accepts 48 VDC input. Both have extended temperature rating (-40 to +75°C), standard filtering, and 250W capacity. They are not interchangeable—choose based on your plant’s available power. If you have standard AC line voltage, use the PFCA. If you have 48 VDC battery banks, use the PCPA.
Q: What’s the difference between DS3815PFCA and DS3815PFLA?
Filtering. The PFCA has standard filtering (<50 mV on 5V). The PFLA has enhanced filtering (<20 mV on 5V). Both accept 240 VAC input, have extended temperature rating, and deliver 250W. If you have sensitive analog measurements, choose the PFLA. If you don’t, the PFCA is the more economical choice.
Q: Can I run this PSU from 120 VAC instead of 240 VAC?
No. The input range is 180-264 VAC only. Feeding 120 VAC will cause the PSU to brown out, and the CPU will repeatedly reset. We’ve seen maintenance crews mis-wire the input thinking “any voltage works” and damage the input stage. If you only have 120 VAC available, you need a step-up transformer or a different PSU variant. Check your panel’s power distribution before ordering.
Q: What’s the correct input terminal configuration?
The input terminals are labeled “L” (Line/Hot), “N” (Neutral), and “GND” (Ground) on the front panel. Connect 240 VAC single-phase to L and N. Ground the chassis via the GND terminal. Do not connect DC to these terminals. Polarity for AC doesn’t matter (L and N can be swapped), but the ground connection is critical for safety and EMI performance.
Q: Can I use this PSU to power a full 15-slot Mark VI rack?
Yes—the PFCA delivers 250W total, sufficient for a fully populated rack in most configurations. At temperatures above 65°C, derating applies. At 75°C, you lose approximately 25% of capacity—down to about 187W. Calculate your actual load and cabinet temperature. The AC input doesn’t change the DC output capacity.
Q: Can I run two PFCA units in redundant configuration?
Yes—the PFCA supports active current sharing for N+1 redundancy. Two units in parallel will each run at approximately 50% load, reducing internal heating and extending component life, especially at high temperatures. Both units must be fed from the same AC source (or synchronized sources) to maintain proper current sharing. We can supply matched pairs tested for current sharing across the full temperature range.
Q: What are the status LED patterns indicating?
Three LEDs on the front panel: DC OK (green), Overload (yellow), Overtemperature (red). Normal: green steady, yellow off, red off. If yellow is steady, you’re in current limit. If red is on, the PSU is overtemperature—check cabinet ventilation.
Q: Is there a fuse on this board that I can replace in the field?
There is an internal input fuse, but it’s not user-replaceable. The fuse is soldered to the PCB and is part of the primary circuit. If the PSU doesn’t power up, it’s likely a wiring issue, blown input fuse, or internal failure. Do not open the casing—the primary side holds dangerous voltages. Send it to us for evaluation.
Q: Can I use a standard 240 VAC DIN-rail power supply instead of this board?
No. The DS3815PFCA is a backplane-specific module with proprietary connector and output ramp timing. The CPU expects the 48V, 24V, and 5V rails to rise within a specific sequence. We’ve seen DIN-rail supplies cause watchdog trips due to timing mismatches. Stick with the original board.
Q: I have a hot environment with only 240 VAC available. Should I choose PFCA or PFLA?
That depends on your analog requirements. If you have sensitive analog measurements (thermocouples, vibration probes, 4-20mA), the PFLA’s enhanced filtering is worth the extra cost. If you don’t have sensitive analog, the PFCA is sufficient and more economical. The PFCA is the workhorse AC-powered PSU for high-temperature environments. The PFLA is the premium version for high-temperature environments with sensitive analog.
Q: Is the PFCA compatible with standard Mark VI racks?
Yes—it fits the same IS200 backplane slot as all other DS3815 PSU variants. No adapter plates or mechanical modifications needed. Direct swap for any other DS3815 PSU—same dimensions, same connector, same terminal layout. No software changes required. Just ensure you’re connecting 240 VAC to the input terminals, not DC.

BENTLY NEVADA 3500/33
HONEYWELL CC-PCNT01
ABB CP450-T-ETH
ABB 3HAC025338-006
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922