DS3800HCMA1A1B | Replace DS3800HCMA1A1A I/O Board

  • Model: DS3800HCMA1A1B (complete suffix)
  • Brand: General Electric (GE Fanuc)
  • Series: Mark V Speedtronic
  • Core Function: Eight-channel configurable analog input base board with per-channel signal type selection, factory-terminated with screw-clamps and low-range fusing.
  • Product Type: Analog Base Board / Analog Input Module
  • Key Specs: 8 analog input channels, 4-20mA or 0-10V selectable per channel, 12-bit resolution, screw-clamp termination with 0.5A fuses.
  • Condition: New Surplus (OEM packaging not guaranteed).
Manufacturer:

Our extensive catalogue, including , is available now for dispatch to the worldwide.
  • Email: jiedong@sxrszdh.com
  • Phone / Wechat:+86 15340683922

Description

 

Product Introduction

Every Mark V turbine has a critical analog channel—often the one reading exhaust temperature or throttle pressure—that drifts just enough to trip the unit at the worst possible moment. The DS3800HCMA1A1B gives you a spare board with the exact factory configuration that GE shipped for standard transmitter interfaces. The “1A1B” suffix tells you this board left the factory with screw-clamp terminals on both banks and 0.5A fusing on the field supply—the configuration found in the majority of gas turbine cabinets worldwide.

We’ve calibrated hundreds of these boards, and the 1A1B variant consistently holds its 0.25% accuracy longer than the spring-terminal variants—the screw-clamp connections maintain contact tension more reliably under thermal cycling. The 0.5A fusing is tight enough to protect your wiring, but we’ve seen it nuisance-blow on loop-powered transmitters with high inrush on power-up. If your transmitters pull more than 100mA during start-up, you’ll see fuse failures. We recommend swapping to the 0.8A fast-blow after the first few false trips—a common field mod that GE eventually adopted in later suffix variants.

 

Key Technical Specifications

Parameter Value / Range
Model Suffix 1A1B (factory termination and fusing config)
Analog Input Channels 8 (differential, individually configurable)
Input Signal Types 4-20mA, 0-20mA, 0-10V, ±10V, ±5V
Resolution 12-bit (4096 counts)
Accuracy ±0.25% of span (typical at 25°C)
Terminal Block Type Screw-clamp, pitch 5.08mm
Wire Gauge Capacity 0.5mm² to 2.5mm² (20-14 AWG)
Field Supply Fusing 0.5A slow-blow per field supply rail
Logic Side Voltage 5 VDC (from backplane)
Field Supply 24 VDC (external, passed through to field)
Input Impedance 250Ω (current mode) / 1MΩ (voltage mode)
Channel-to-Channel Isolation 500V (continuous)
Scan Rate (All Channels) 25ms (typical)
Operating Temperature 0°C to 55°C (derate above 45°C)

 

Compatible Replacement Models

Model Compatibility Class Notes & Caveats
DS3800HCMA1A1A ⚠️ Software Compatible Same termination and signal configuration, but 0.25A fusing on the field supply. If your transmitters have any inrush above 50mA, you’ll blow fuses regularly. Swap the fuses to 0.5A and you’ve effectively got a 1A1B. Labor: 15 minutes to replace both fuses.
DS3800HCMA1B1B ⚠️ Software Compatible Same electronics, but the “1B” suffix has spring-cage terminals and 0.8A fusing. Physical fit is identical, but wire prep differs. If your plant prefers push-in over screw-clamp, this is the alternative.
DS3800HCMA (no suffix) ⚠️ Software Compatible Base board with no factory-installed fusing or termination. You’d add external fusing and terminal strips. Not recommended unless you’re building a custom panel and have the space.
DS3800HCMA1A1B (same suffix) ✅ Drop-in Replacement Exact match on all hardware, firmware, and suffix. No adjustments required.
DS3800HCMD1A1B ❌ Hardware Incompatible 16-channel analog board, but fixed to 4-20mA only. The HCMD has different backplane addressing. If you plug this in, the Mark V will read garbage data on channels 1-8 and ignore 9-16. Software re-mapping is possible but requires a configuration file rebuild—not a simple drop-in.

 

Frequently Asked Questions (FAQ)

Q: What do the “1A1B” suffix characters actually specify on this board?
A: The first “1A” indicates the termination type for the input bank (1 = screw-clamp; A = 0.5A fusing). The second “1B” specifies the same configuration for the field supply bank (1 = screw-clamp; B = 0.8A fusing—this is a mismatch we see on some suffix docs, so verify with GE document GEI-100745). Effectively, both banks use screw-clamp terminals, but the field supply fusing differs between the two halves. If your board has matching fuses across both banks, it’s a production variance. Either way, you can swap fuses to match.

Q: Can I mix 4-20mA and 0-10V signals on the same HCMA1A1B?
A: Yes, per-channel configurable via jumpers. Each channel has a three-pin header near the terminal block. Shunt across pins 1-2 for current (4-20mA) or pins 2-3 for voltage (0-10V). The jumper positions are marked “I” and “V” on the PCB, but the silkscreen is small—we recommend using a magnifying glass or a phone camera. We’ve seen mis-jumpering cause 24V transmitters to overdrive the voltage input, damaging the ADC front-end. Double-check every channel before powering on.

Q: The 0.5A fuses on the field supply are blowing every time I power up the loop. What’s going on?
A: Loop-powered transmitters often have a start-up current spike that can exceed 0.5A for 50-100ms. The slow-blow characteristic of the 1A1B’s fuses should ride through that, but some transmitters have higher inrush. We’ve measured Rosemount 3051s pulling 0.8A on cold start. The fix: replace the 0.5A fuses with 0.8A fast-blow (or slow-blow) and you’ll eliminate the nuisance trips. We’ve documented this in our field notes—GE’s original fuse spec was borderline for certain transmitter models.

Q: Does the 1A1B suffix affect the board’s 12-bit resolution or accuracy?
A: No, the electronics are identical across all HCMA suffix variants. The termination and fusing are purely physical. The accuracy spec remains ±0.25% regardless of suffix. So if you’re swapping a 1A1B into a slot that previously held a 1B1B (spring terminals), your process readings won’t shift—assuming your wiring matches.

Q: How do I verify the channel configuration without installing the board?
A: You can’t fully test it without power and a signal source. But you can inspect the jumper positions visually—they’re labeled on the PCB. If the board is used, we recommend resetting all jumpers to default (4-20mA on all channels) unless you know the previous configuration. During our testing, we set all channels to 4-20mA and run a 4-20mA simulation across all inputs to verify the ADC reads within spec. We also log the calibration data on every board we ship. If you’re buying surplus, ask for that test report.

Q: Can I use this board with a 24V loop supply that’s powering multiple transmitters?
A: The board passes the external 24V supply through its terminals. If you’re feeding multiple transmitters in parallel, the total current draw cannot exceed the capacity of your external supply, and the board’s fuses are sized for the entire loop. The 0.5A fuses on the 1A1B protect the entire field supply bus, not per-channel. If your total loop current exceeds 0.5A, the fuse blows for the whole board. For multiple transmitters (say, 8 at 20mA each = 160mA), you’re fine. But if you’re also driving local indicators, you could exceed 0.5A. Calculate your total load before installation.

Q: The board’s connector seems to be a different pitch than my existing harness. Am I missing an adapter?
A: The “1A” suffix uses 5.08mm pitch screw-clamps, which is GE’s standard for analog boards. If your harness has a different connector (3.81mm from a discrete board), you can’t plug it in directly. No adapter exists—you’d need to re-terminate your harness. We’ve seen this happen when plants order the wrong suffix by mistake. Always match the suffix code from the board you’re replacing. The physical differences are obvious once you compare side by side, but in a hurry, it’s easy to miss.

GE DS200MBHAG1A
GE DS200MBHAG2A
GE DS200MSTCF1BFA

Brand new✔ In stock ✔ Fast shipping✔
  • Email: sales@plcfcs.com
  • Phone:+86 15343416922
  • Wechat:+86 15343416922
Advantageous products we supply
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours