Description
Product Core Brief
- Model: DS200SSBBG1A
- Brand: General Electric (GE)
- Series: Mark V DS200
- Core Function: Safety fieldbus communication board
- Product Type: Safety Bus Gateway (2 Ethernet ports)
- Key Specs: PROFIsafe | CIP Safety | SIL 3 | 200 byte safety I/O | Redundant Ethernet
- Condition: New Original.
Product Introduction
The DS200SSBBG1A is a safety bus communication board for GE’s Mark V DS200 series, used in Safety Instrumented Systems (SIS) for turbine control. It connects the Mark V to PROFIsafe (Profinet) and CIP Safety (EtherNet/IP) safety networks, allowing safety data exchange with SIL 3 certified PLCs and safety I/O.
The SSBBG1A acts as a safety gateway between the Mark V backplane and industrial safety networks. It supports PROFIsafe over Profinet and CIP Safety over EtherNet/IP (selectable). Safety data (up to 200 bytes) is exchanged with the safety master (e.g., Siemens S7-1500F, Rockwell ControlLogix with GuardLogix). The board is TÜV certified for SIL 3 per IEC 61508.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Safety protocols | PROFIsafe (Profinet), CIP Safety (EtherNet/IP) |
| Ethernet ports | 2 x RJ45 (integrated switch, 10/100 Mbps) |
| Safety I/O data | 200 bytes input, 200 bytes output |
| Communication cycle time | 10 ms typical |
| Safety integrity level | SIL 3 (IEC 61508, IEC 61511) |
| PROFIsafe version | V2.4 (supports F-Parameters) |
| CIP Safety version | CIP Safety V2.5 |
| Redundancy | Media Redundancy Protocol (MRP) |
| Configuration | Web browser (HTTPS) |
| Diagnostic coverage | >99% (F-CPU required in safety master) |
| Proof test interval | 1 year (automatic self-test) |
| Isolation (Ethernet to backplane) | 2500 VAC |
| Operating temperature | −40°C to +70°C |
| Backplane current | 5 VDC @ 600 mA |
| Dimensions | 6U x 4HP x 160 mm (single slot) |
| Accessories | SIL 3 certificate, safety manual, configuration guide, Ethernet cables |
Key Selling Points & Differentiators
- SIL 3 certified safety communication – TÜV certified for use up to SIL 3. Connect Mark V to PROFIsafe or CIP Safety networks.
- PROFIsafe over Profinet – Direct connection to Siemens S7-1500F, S7-1200F, ET200SPF safety PLCs.
- CIP Safety over EtherNet/IP – Direct connection to Rockwell ControlLogix with GuardLogix, CompactLogix with GuardLogix.
- 200 bytes safety I/O – Exchange safety data with the safety master. Typically trip commands, interlock statuses.
- Integrated Ethernet switch – Daisy-chain multiple safety devices or connect to redundant networks. MRP support.
- F-parameter configuration – Configure F_Dest, F_Source, F_WD_Time via web interface.
- Safety bus diagnostics – Monitor communication status, CRC errors, watchdog timeouts.
- QC includes SIL 3 communication test – Verified with Siemens S7-1500F and Rockwell GuardLogix.
- 5-year warranty
Frequently Asked Questions (FAQ)
Q: What is the difference between standard communication (SLCCG) and safety communication (SSBBG)?
| Feature | SLCCG (Standard) | SSBBG (Safety) |
|---|---|---|
| Safety certification | No | SIL 3 (TÜV) |
| PROFIsafe | No | Yes |
| CIP Safety | No | Yes |
| Safety data integrity | CRC-16 | CRC-32 + F-Parameters |
| Watchdog | Software | F_WD_Time (safety) |
Q: Can the SSBBG1A be used as a standard (non-safety) communication board?
A: Yes—the board also supports standard Profinet IO and EtherNet/IP. However, for standard communication, use SLCCG1A (lower cost). SSBBG includes safety features not needed for non-safety applications.
Q: How do I configure the board for PROFIsafe?
A: Connect PC to Ethernet port. Open web browser, navigate to board IP address. Select PROFIsafe mode. Enter F-parameters: F_Dest, F_Source, F_WD_Time. Download configuration. In Siemens TIA Portal, add board as PROFIsafe device using GSDML file (included).
Q: What is F_WD_Time?
A: Watchdog time for safety communication. If safety master does not send a new safety telegram within this time, board sets outputs to failsafe state. Typical setting: 100–500 ms.
Q: How many safety bytes can I exchange?
A: 200 bytes input, 200 bytes output. This includes safety data plus standard data (if configured). For typical turbine safety, 32 bytes is sufficient.
Q: What QC tests are specific to the SSBBG1A?
A: Ten tests:
- PROFIsafe conformance: with Siemens S7-1500F, SIL 3 communication, 72 hours
- CIP Safety conformance: with Rockwell GuardLogix, SIL 3, 72 hours
- F-parameter verification: F_Dest, F_Source, F_WD_Time accuracy
- Safety data integrity: inject CRC errors, verify failsafe
- Watchdog test: stop safety master, verify failsafe within F_WD_Time
- Ethernet redundancy: MRP ring break, recovery <50 ms
- Isolation: 3000 VAC Ethernet to backplane
- Diagnostic coverage: >99% via fault injection
- Temperature: −40°C to +70°C
- Burn-in: 168 hours at +65°C, continuous safety communication
Q: What shipping protection?
A: Anti-static bag, ESD foam cradle, hard plastic clamshell case, desiccant. Double-wall box with “SAFETY CERTIFIED,” “SIL 3” labels. SIL 3 certificate laminated. Safety manual (150 pages) included. Configuration guide included. Ethernet cables included. Each board ships individually. Factory site visit recommended for first-time safety integration. Contact us for safety application engineering support.

APP-ETH-PCU PLC DCS
APP-ETH-PCU-C PLC DCS
APP-EPB-PCU PLC DCS
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922