Product Core Brief
- Model: DS200SSBAG1BAA
- Brand: General Electric (GE)
- Series: Mark V DS200
- Core Function: High performance safety shutdown board
- Product Type: High Speed Safety Board (4 relays, 16 inputs, 4 MPU)
- Key Specs: <5 ms response | 4 x 10 A relays | 16 x 24 V inputs | 4 x MPU | 0.01% speed accuracy
- Condition: New Original.
Product Introduction
The DS200SSBAG1BAA is a high-performance safety shutdown board for GE’s Mark V DS200 series, used in Speedtronic turbine control systems. It provides ultra-fast response (<5 ms), 16 discrete inputs, and 4 overspeed inputs with 0.01% speed measurement accuracy.
The “BAA” suffix represents the high-performance variant of the safety shutdown family. Features: <5 ms response time (4x faster than SSBAG1B), 16 SIL 2 certified discrete inputs, 4 magnetic pickup inputs with digital signal processing (0.01% speed accuracy), and enhanced diagnostics with event logging. Use it for high-speed turbine overspeed protection, generator synchronization safety, or any application requiring the fastest possible safety response.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Safety relay outputs | 4 (Form C, redundant pairs) |
| Contact rating | 10 A @ 250 VAC / 30 VDC |
| Response time (input to relay) | <5 ms |
| Discrete inputs | 16 x 24 VDC (SIL 2 certified) |
| Discrete input diagnostics | Open-wire, short-circuit, stuck-at |
| Discrete input response | <2 ms |
| Overspeed inputs | 4 x magnetic pickup (redundant pairs) |
| MPU frequency range | 5 Hz to 20 kHz |
| MPU threshold | Auto-calibrating (5–60 VAC) |
| Speed measurement accuracy | ±0.01% of reading |
| Speed measurement resolution | 0.1 Hz |
| Overspeed trip setpoint | Programmable (via configuration) |
| Voting architecture | 1oo2 per channel, 2oo2 cross-channel |
| Diagnostic coverage | >95% |
| Event logging | 1000 events (time-stamped) |
| Isolation | 2500 VAC |
| Operating temperature | −40°C to +75°C |
| Dimensions | 6U x 4HP x 160 mm (single slot) |
| Accessories | Configuration software (USB), programming cable, MPU calibration tool, diagnostic guide, safety manual |
Key Selling Points & Differentiators
- <5 ms response time – Fastest safety board in Mark V family. Critical for overspeed protection on high-speed turbines (aeroderivatives, generators).
- 4 x overspeed inputs with 0.01% accuracy – Digital signal processing. No potentiometers. Auto-calibration. Speed measurement accurate to 0.01%.
- 16 x SIL 2 discrete inputs – Connect emergency stops, vibration trips, temperature switches. Per-channel diagnostics.
- Programmable overspeed setpoint – Configure via software. Two independent setpoints: alarm and trip.
- Event logging (1000 events) – Time-stamped record of all trips, input changes, and diagnostic events. Download via USB.
- Auto-calibrating MPU inputs – No manual threshold adjustment. Board learns sensor characteristics on startup.
- Diagnostic coverage >95% – Suitable for SIL 2 applications with reduced proof test interval.
- QC includes <5 ms response verification – Every board tested at 4 kHz input rate.
- 5-year warranty
Frequently Asked Questions (FAQ)
Q: What is the difference between SSBAG1B (enhanced) and SSBAG1BAA (high performance)?
| Feature | SSBAG1B | SSBAG1BAA |
|---|---|---|
| Response time | <10 ms | <5 ms |
| Discrete inputs | 12 | 16 |
| Overspeed inputs | 2 | 4 |
| Speed accuracy | ±1% | ±0.01% |
| MPU calibration | Manual pot | Auto-calibrating |
| Event logging | No | Yes (1000 events) |
| Configuration | Jumpers | Software |
Q: How does auto-calibrating MPU work?
A: On power-up, the board measures the MPU output at zero speed (residual voltage). During operation, it measures peak voltage at running speed. Threshold is set to 50% of running voltage (configurable). No potentiometer adjustments. Re-calibrates every 24 hours for sensor drift.
Q: What is the minimum overspeed detection time?
A: At 60 Hz (3600 rpm), one cycle is 16.6 ms. The board detects overspeed within one cycle plus 5 ms response = 21.6 ms worst case. At higher frequencies (12 kHz MPU output), detection is faster.
Q: How do I configure the board?
A: Connect PC to USB port on board front panel. Run included Windows software. Set: overspeed trip setpoint (Hz), overspeed alarm setpoint, input mapping (AND/OR logic), and relay configuration. Save to board flash. No jumpers on BAA revision.
Q: What is the event log?
A: Board stores last 1000 events: timestamp (ms since power-up), event type (input change, relay change, trip, diagnostic fault, configuration change). Download via USB as CSV. Use for post-trip analysis.
Q: What QC tests are specific to the BAA revision?
A: Twelve tests:
- Response time: <5 ms (oscilloscope)
- Discrete inputs: 16 channels, threshold <5 V OFF, >15 V ON
- MPU auto-calibration: 5–60 VAC, 20 Hz–20 kHz
- Speed accuracy: ±0.01% verified with signal generator
- Overspeed trip: programmable setpoint accuracy ±0.1 Hz
- Event logging: write 1000 events, read back
- Relay operate: 1000 cycles at 5 A
- Isolation: 3000 VAC
- Diagnostic coverage: >95% via fault injection
- Temperature: −40°C to +75°C
- USB configuration: read/write verify
- Burn-in: 168 hours at +65°C
Q: What shipping protection?
A: Anti-static bag, ESD foam cradle, hard plastic clamshell case, desiccant. Double-wall box with “HIGH PERFORMANCE,” “SAFETY CRITICAL” labels. Configuration software on USB drive. Programming cable included. Each board ships individually. Factory site visit recommended for first-time configuration. Contact us for application engineering support.

APP-PFB-PCI PLC DCS
APP-PFB-PCIE PLC DCS
APP-PF2-PCI PLC DCS
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922