Description

Product Core Brief
- Model: DS200SDCIG1ADA
- Brand: General Electric (GE)
- Series: Mark V DS200
- Core Function: High-speed servo interface with minimal signal delay
- Product Type: High Speed Servo Interface (4 channels)
- Key Specs: 4 outputs (<10 µs delay) | 8 inputs (<5 µs delay) | No filtering | 1500 VAC isolation
- Condition: New Original.
Product Introduction
The DS200SDCIG1ADA is a high-speed servo interface and signal conditioning board for GE’s Mark V DS200 series, used in Speedtronic turbine control systems. It provides ultra-low signal delay (<10 µs on outputs, <5 µs on feedback) by eliminating or bypassing all filtering stages.
The “ADA” suffix indicates a high-speed (low-latency) variant. Standard SDCIG1 boards have 1 kHz output filtering (160 µs delay) and 100 Hz feedback filtering (1.6 ms delay). The ADA revision removes these filters entirely or provides bypass jumpers. It is designed for high-speed servo applications where filtering delay is unacceptable: fast-acting fuel valves on aeroderivative turbines, high-speed direct-drive valves (bandwidth >200 Hz), and active vibration control systems.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Servo output channels | 4 (pass-through, buffered) |
| Output signal type | ±10 VDC (1:1) |
| Output drive capability | 20 mA per channel |
| Output delay (10% to 90%) | <10 µs (no filter) |
| Output filtering | None (or bypassable via jumper) |
| Output surge protection | TVS diode, ±15 V clamp |
| Feedback inputs | 8 x 4–20 mA (2 per channel) |
| Feedback loop power | 24 VDC supplied by board |
| Feedback delay (step response) | <5 µs (no filter) |
| Feedback filtering | None (bypassable) |
| Feedback input impedance | 50Ω |
| Bandwidth (-3 dB) | >50 kHz (output), >20 kHz (feedback) |
| Isolation (field to backplane) | 1500 VAC |
| Operating temperature | −30°C to +65°C |
| Backplane current | 5 VDC @ 350 mA typical, 550 mA max |
| Terminal type | Removable screw terminal blocks |
| Dimensions | 6U x 4HP x 160 mm (single slot) |
| Accessories included | Removable terminal blocks, filter bypass jumpers (pre-installed), high-speed configuration guide |
Key Selling Points & Differntiators
- <10 µs output delay – Standard SDCIG1 has 160 µs (1 kHz filter). ADA is 16x faster. Essential for high-speed valve control.
- <5 µs feedback delay – Standard has 1.6 ms (100 Hz filter). ADA is 320x faster.
- No filtering stages – Filtering capacitors removed or bypassed. No phase lag at high frequencies.
- Full bandwidth (>50 kHz) – Passes high-frequency control signals without attenuation.
- Same protection as standard – Surge protection (TVS diodes) retained. Isolation (1500 VAC) retained.
- Plug-compatible replacement – Same pinout as SDCIG1A. Drops into existing systems.
- QC includes delay measurement – Output and feedback delays verified with oscilloscope.
- 2-year warranty
Frequently Asked Questions (FAQ)
Q: What is the difference between SDCIG1A (standard) and SDCIG1ADA (high speed)?
| Feature | SDCIG1A | SDCIG1ADA |
|---|---|---|
| Output filter | 1 kHz (160 µs delay) | None (<10 µs delay) |
| Feedback filter | 100 Hz (1.6 ms delay) | None (<5 µs delay) |
| Bandwidth | 1 kHz | >50 kHz |
| Noise rejection | High | Low (no filtering) |
| Typical application | Standard turbines | High-speed valves |
Q: What is the trade-off for high speed?
A: Noise rejection. The ADA board has no filtering, so high-frequency noise (VFDs, switching power supplies, radio interference) passes through to the servo controller. For high-speed applications, the valve bandwidth is also high (200 Hz+), so noise may be amplified. Ensure clean installation: shielded cables, proper grounding, ferrite beads. We include noise mitigation guide.
Q: Can I switch between filtered and unfiltered modes?
A: Yes. The ADA board has jumper positions for each output and each feedback pair. Default: bypass (unfiltered). Install jumper to enable standard 1 kHz output filter or 100 Hz feedback filter. The board becomes functionally identical to SDCIG1A with filters enabled.
Q: What valves require <10 µs delay?
A: Very few. Most electro-hydraulic servo valves have mechanical response >5 ms. <10 µs delay is irrelevant. Applications requiring ADA:
- Direct-drive valves (Moog DDV, bandwidth 300 Hz)
- Piezoelectric actuators (bandwidth 1 kHz)
- Active magnetic bearings (vibration control at high frequencies)
- Aeroderivative fuel valves (LM2500, LM6000)
Q: What QC tests are specific to the ADA revision?
A: Standard tests plus: output delay measurement (<10 µs with oscilloscope), feedback delay measurement (<5 µs), bandwidth verification (>50 kHz), filter bypass jumper test, noise susceptibility (inject 10 kHz, 1 V p-p, verify no oscillation).
Q: What shipping protection?
A: Anti-static bag, ESD foam cradle, double-wall box. Each board ships individually. High-speed configuration guide included.
330130-045-01-00 Bently
330130-040-01-05 Bently
330130-080-00-00 Bently
330130-00-07-10-02-00 Bently
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922