Description
Product Introduction
The DS200PCCAG8ACB is a power entry board from GE’s Mark V DS200 series, designed specifically for heavy-duty gas and steam turbine control cabinets. It handles primary AC/DC conversion, distributes control power to I/O racks, and provides overcurrent protection for critical logic circuits.
Unlike lower-tier power modules, this board delivers isolated 24 VDC with active voltage monitoring and fault reporting back to the main CPU. Field data shows it reduces noise-related shutdowns by 40% compared to unregulated supplies. No firmware to mismatch—pure hardware reliability.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input voltage range | 90–264 VAC or 125–250 VDC (auto-sensing) |
| Output voltage 1 | +24 VDC ±2% @ 8 A continuous |
| Output voltage 2 | +5 VDC @ 10 A (backplane logic) |
| Maximum total load | 15 A |
| Isolation rating | 1500 VAC input-to-output |
| Operating temperature | −30°C to +65°C |
| Storage temperature | −40°C to +85°C |
| Protection | Overvoltage (clamp at 28 V), short circuit, thermal |
| Connector type | 64-pin DIN 41612 + barrier terminal strip |
| Status indicators | LED for +24V OK, +5V OK, input power |
| Form factor | 6U x 4HP x 160 mm depth |
Key Selling Points & Differentiators
- Live-tested at nominal load (24 V @ 5 A for 24 hrs) – Verifies thermal stability and ripple under 50 mV peak-to-peak.
- No firmware version mismatch – Unlike CPU modules, this analog/digital power board works out of the box with any Mark V rack.
- Input auto-ranging – Works with 110 VAC control power or 250 VDC battery banks; no DIP switch or jumper changes needed.
- QC includes insulation resistance check – Verified >20 MΩ between primary and secondary (exceeds GE spec of 10 MΩ).
- Direct replacement for earlier revs – Backward compatible with DS200PCCAG8A, 8B, 8C; same pinout, higher output capacitor rating.
- 2-year warranty – Covers functional failure; standard 30-day return for incompatibility or DOA (less than 0.5% in our test pool).
Frequently Asked Questions (FAQ)
Q: Can I hot-swap this board while the Mark V rack is powered?
A: No. To be frank, the DS200 series backplane was not designed for hot-plug. Power down the entire rack, wait 2 minutes for capacitors to discharge, then swap. We’ve seen field technicians damage the backplane connector trying to hot-swap.
Q: This is a surplus board. How do I know it wasn’t damaged by ESD or prior failure?
A: Our QC process includes visual magnification (10x) for burnt traces or cracked solder joints, followed by a full load test on a known-good Mark V test rack. We also log insulation resistance before and after the 24-hour burn-in. You’ll get a printed QC pass sheet with each board.
Q: What’s the difference between DS200PCCAG8ACB and the older DS200PCCAG8A?
A: The ACB revision replaces the input rectifier bridge with a higher-rated 35 A part (original was 25 A) and adds a metal-oxide varistor for surge suppression. Pinout and mounting holes are identical. No software or configuration changes required.
Q: Will this work with a Mark VI or Mark VIe system?
A: No. Physically different backplane and voltage sequencing. We’ve seen customers try to force it—the connectors don’t align, and voltage levels are incompatible. Stick to Mark V only.
Q: What’s your return policy if I order the wrong part?
A: 30 days from delivery for uninstalled, ESD-protected boards. We charge a 15% restocking fee after 15 days. No returns if you’ve soldered wires directly to the terminal block. Honest advice: Photograph your existing board’s full model string and barrier strip wiring before ordering.
Q: Does this board store any turbine configuration or tuning parameters?
A: No. It’s purely power distribution. You will not lose programming or speed/load tuning by replacing this board. The CPU flash memory and RAM are on a separate board (DS200CPCAG or similar).
Q: What shipping ESD protection do you use?
A: Anti-static bag (dissipative, <10 nC charge) inside corrugated cardboard with conductive foam under the PCB. We also include a humidity indicator card—if pink, we re-dry and repack. No corners cut here.

5SHY3545L0009 3BHB013085R0001 PLC DCS
NTA105PS05WL PLC DCS
IMD004 PS002Y PLC DCS
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922