Description
Product Introduction
The 531X122PCNALG2 is the ultimate power supply for the Mark V system—delivering the absolute highest hold-up time (195ms) of any Mark V power supply ever produced. With the full suite of diagnostic capabilities, it’s the supply you install when power continuity is the single most critical factor in your turbine control system.
Compared to the 531X122PCNALG1, the “G2” revision extends hold-up from 190ms to 195ms and reduces inrush current from 23A to 22A. The terminal assignment is identical—direct drop-in. No firmware changes required.
Key Technical Specifications
| Parameter | Value / Range |
|---|---|
| AC Input Voltage | 200–240 VAC ±10% (no 120V operation) |
| Input Frequency | 47–63 Hz |
| Input Current (Max) | 9.0 A @ 240VAC |
| Power Factor | >0.99 (active PFC) |
| Inrush Current (Cold Start) | 22A peak @ 240VAC |
| DC Output Voltage | 24 VDC ±1% (fixed) |
| Remote Sense Compensation | Up to 2.5V drop (adjustable) |
| Output Current (Continuous) | 66.6 A (1600W) |
| Output Current (Peak, 10s) | 80.0 A |
| Hold-up Time | 195 ms @ full load |
| Ripple & Noise | < 50 mV p-p |
| Efficiency | 96% typical |
| Protections | Overvoltage, overcurrent, overtemperature, short-circuit |
| Redundancy | Parallel operation with OR-ing diodes + hardware load-sharing |
| Load-Sharing Accuracy | ±1% |
| Diagnostic Output | RS-485 (Modbus RTU) – 30+ registers |
| Data Logging | 10,000 fault events (time-stamped) |
| Log Download | USB Type B |
| Status Indicators | DC OK, Fault, Overload, Fan, Load Share, Remote Sense, Diagnostic, Data Log Full, USB Active |
| Cooling | Modular fan cartridge (dual 92mm ball-bearing fans, 50 CFM) |
| Fan Replacement | Swap entire cartridge—no individual fan replacement |
| Termination | Screw terminal (input) + 24-pin backplane + 2-pin remote sense + 3-pin RS-485 + USB Type B |
| Operating Temp | 0°C to +60°C |
| Dimensions | 280 x 120 x 85 mm |
Compatible Replacement Models
| Model | Classification | Notes |
|---|---|---|
| 531X122PCNALG2 | ✅ Drop-in Replacement | Target model. No changes. |
| 531X122PCNALG1 | ✅ Drop-in Replacement | 190ms hold-up, 23A inrush. Direct swap. |
| 531X122PCNALG | ✅ Drop-in Replacement | Original revision—0.95 PFC, 50ms hold-up, no diagnostics. Direct swap. |
| 531X122PCNAKG1 | ✅ Drop-in Replacement | 180ms hold-up, 10,000-event log. Direct swap—the NALG2 has longer hold-up. |
| 531X121PCRALG1 | ✅ Drop-in Replacement | 190ms hold-up, 10,000-event log. Direct swap—the NALG2 has longer hold-up. |
| 531X121PCRALG2 | ✅ Drop-in Replacement | 190ms hold-up, 10,000-event log. Direct swap—the NALG2 has longer hold-up. |
| DS3800NPSA | ❌ Hardware Incompatible | Mark IV supply—different form factor. |
Frequently Asked Questions (FAQ)
Q: What’s the difference between the NALG2 and the NALG1?
The NALG2 has longer hold-up (195ms vs. 190ms) and lower inrush (22A vs. 23A). It represents the absolute peak of Mark V power supply performance. If you need the maximum hold-up time available for the Mark V system, this is the supply you want.
Q: The Fault LED is red, but the DC OK LED is green. What’s happening?
Green DC OK means the 24V output is within spec. Red Fault indicates an internal warning—typically overtemperature (fan failure) or input voltage out of range. The data logger captures the fault, and the USB port allows quick log download for analysis.
Q: Can I run two NALG2 supplies in parallel for redundancy?
Yes—the NALG2 has OR-ing diodes and hardware load-sharing. Connect DC outputs together (+24V to +24V, 0V to 0V), connect load-share signal terminals together, connect remote sense terminals together, connect RS-485 terminals together (daisy-chain), and feed AC inputs from separate breakers. The supplies share the load within ±1%. Each supply has its own data log.
Q: Can I hot-swap the NALG2 while the rack is powered?
Yes, in redundant configurations (two supplies in parallel). In a single-supply config, pulling the supply shuts down the rack. If redundant, verify the OR-ing diodes are present before pulling one.
Q: What’s the expected lifespan of the NALG2?
The electrolytic capacitors are rated for 12,000 hours at 85°C. In a 40°C cabinet, the lifespan extends to about 18-22 years. The modular fan cartridge with dual ball-bearing fans is rated for 80,000 hours at 40°C (about 9.1 years). Replace the fan cartridge every 5-7 years proactively.
Q: What’s the lead time for a surplus unit?
We keep 2-3 units in stock. Domestic: 2-3 business days ground, overnight if ordered by 2 PM EST. International: 5-7 days via DHL, with customs potentially adding 1-3 days. We include a GE certificate of origin and commercial invoice with every shipment. Contact us if you need expedited shipping.

BENTLY 330851-02-000-070-10-00-05
PTM PSMU-350-3
ABB 3AFE61320946P0001
Kollmorgen CB06560
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922

Wechat:+86 15343416922