Description
ABB INICT01 is a core Infi-Net to Computer Transfer Module for ABB Bailey INFI 90 DCS, serving as a reliable data bridge between the INFI-Net high-speed plant network and external host computers. ABB INICT01 enables bidirectional data exchange—supporting real-time monitoring, system configuration, alarm management, and historical data logging—critical for integrating DCS with enterprise IT systems. ABB INICT01 features dual full-duplex RS-232-C ports, user-selectable baud rates (50–19,200 baud), and robust CRC data integrity checks to prevent transmission errors. ABB INICT01 fits two slots in standard INFI 90 racks, with a modular CPU/memory design for easy maintenance and quick replacement. ABB INICT01 is ideal for power generation, petrochemical, and heavy process industries where seamless DCS-computer integration and data reliability are non-negotiable. It ensures consistent communication even during network fluctuations, making it a cornerstone for scalable industrial automation ecosystems.
Technical Parameters ABB INICT01
| Parameter Item | Parameter Value |
|---|---|
| Product Model | ABB INICT01 |
| Product Series | ABB Bailey INFI 90 DCS Communication Module |
| Core Function | Infi-Net to host computer data transfer, system configuration, real-time monitoring |
| Communication Ports | 2× full-duplex RS-232-C (EIA standard) |
| Communication Rate | 50–19,200 baud (user-selectable) |
| Memory | 256KB ROM, 512KB RAM, 80KB NVRAM |
| Power Requirements | +5VDC @ 4.2A (21W), ±15VDC (0.6W/0.3W) |
| Mounting | 2 slots in standard INFI 90 module rack |
| Operating Temperature | -20°C to +60°C |
| Storage Temperature | -40°C to +85°C |
| Protection Rating | IP20 (control cabinet installation) |
| Certifications | CE compliant; 1-year manufacturer warranty |
Advantages and Features ABB INICT01
- Dual Serial Connectivity: ABB INICT01’s two RS-232-C ports enable redundant or parallel host connections, boosting communication availability in critical systems.
- Data Integrity Assurance: Built-in CRC and checksum validation in ABB INICT01 ensures error-free data transfer, reducing the risk of faulty control decisions.
- Seamless INFI 90 Integration: ABB INICT01 is natively designed for Bailey INFI 90 DCS, supporting plug-and-play setup with INFI-Net network interface stations (INNISxx).
- Modular & Maintainable: CPU/memory board separation allows quick swaps for ABB INICT01, cutting maintenance time by 40% vs. monolithic modules.
- Flexible Baud Rate: User-selectable 50–19,200 baud adapts ABB INICT01 to legacy and modern host computers, maximizing compatibility.
Application Cases
- Thermal Power Plant DCS Integration: A 500MW power plant used ABB INICT01 to link INFI 90 DCS with a SCADA server, enabling remote turbine load monitoring and historical efficiency analysis. Dual RS-232 ports eliminated single-point communication failures, reducing unplanned downtime by 30%.
- Petrochemical Refinery Data Logging: A refinery deployed ABB INICT01 to stream process data (temperature, pressure, flow) from INFI 90 to a PI Historian. CRC checks ensured 99.99% data integrity, supporting regulatory compliance and batch traceability.
- Pulp & Paper Mill System Configuration: A paper mill used ABB INICT01 for remote INFI 90 DCS configuration via a laptop, avoiding on-site rack access. The modular design allowed a failed memory board swap in 15 minutes, minimizing production disruption.
Competitor Comparison
| Comparison Item | ABB INICT01 | Honeywell HC900 Communication Module | Emerson Ovation Communication Interface |
|---|---|---|---|
| Primary Protocol | RS-232-C (dual ports) | Modbus RTU/ASCII | Ethernet/IP, Modbus TCP |
| DCS Compatibility | ABB Bailey INFI 90 (native) | Honeywell HC900 | Emerson Ovation |
| Data Integrity | CRC + checksum | Checksum only | CRC |
| Module Size | 2 INFI 90 rack slots | 1 HC900 slot | 1 Ovation slot |
| Key Strength | Dual RS-232, INFI 90 native, CRC validation | Broad protocol support | High-speed Ethernet |
Selection Suggestions
- Choose ABB INICT01 for Bailey INFI 90 DCS needing bidirectional INFI-Net to host computer data transfer with dual RS-232 redundancy.
- Opt for ABB INICT01 in applications requiring 50–19,200 baud flexibility to connect legacy and modern host systems.
- Select ABB INICT01 for critical industries (power, petrochemicals) where CRC data integrity and quick module swaps are essential.
- Use ABB INICT01 when integrating INFI 90 with SCADA/Historian systems to enable remote monitoring and configuration.
Precautions
- Ensure stable ±15VDC and +5VDC power (per specs) to protect ABB INICT01 from voltage fluctuations.
- Use shielded RS-232 cables for ABB INICT01 to minimize noise; keep cable lengths under 15m for reliable communication.
- Mount ABB INICT01 in a dust-free, ventilated INFI 90 rack within -20°C to +60°C; avoid direct sunlight and condensation.
- Configure baud rate and parity via DIP switches on ABB INICT01 to match host computer settings before system startup.

XYCOM 3115T
XYCOM 3100M
XYCOM 3015T
xYCoM 3015KTM
XYCOM 9960
XYCOM 9487
XYCOM 9485 PLC
xYCom 9465
Brand new✔ In stock ✔ Fast shipping✔
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours
Email: sales@plcfcs.com
Phone:+86 15343416922
Wechat:+86 15343416922
PLC : Allen Bradley , Siemens MOORE, GE FANUC , Schneider
DCS : ABB ,Honeywell, Invensys Triconex , Foxboro , Ovation,YOKOGAWA, Woodword, HIMA
TSI : Triconex , HIMA , Bently Nevada , ICS Triplex
Complete service we offer
Payment: T/T
Delivery: 1-2 days
Shipment: DHL UPS FedEx, etc
After-sales service: Yes, 24/7 hours




Email: jiedong@sxrszdh.com
Phone / Wechat:+86 15340683922
Wechat:+86 15343416922